Water Temp. And Flows - York YCAV0267E Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

LEAVING WATER
MODEL
TEMPERATURE (°F)
NUMBER
YCAV
MIN.
1
0267(E/V)
40
0287(S/P/E/V)
40
0307(S/P)
40
0327(E/V)
40
0357(S/P/E/V)
40
0397(S/P)
40
0397(E/V)
40
0417(S/P)
40
0417(E/V)
40
0457(S/P)
40
0477(S/P/E/V)
40
0507(S/P)
40
0527(S/P)
40
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest YORK office for application guidelines.
LEAVING WATER
MODEL
TEMPERATURE (°C)
NUMBER
YCAV
MIN.
1
0267(E/V)
4.4
0287(S/P/E/V)
4.4
0307(S/P)
4.4
0327(E/V)
4.4
0357(S/P/E/V)
4.4
0397(S/P)
4.4
0397(E/V)
4.4
0417(S/P)
4.4
0417(E/V)
4.4
0457(S/P)
4.4
0477(S/P/E/V)
4.4
0507(S/P)
4.4
0527(S/P)
4.4
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 60°F (15.6°C), contact the nearest YORK office for application guidelines.
JOHNSON CONTROLS
WATER TEMPERATURE AND FLOWS
(English Units)
MAX.
MIN.
2
60
250
60
250
60
300
60
300
60
300
60
300
60
350
60
350
60
400
60
350
60
400
60
400
60
400
WATER TEMPERATURE AND FLOWS
(SI Units)
MAX.
MIN.
2
15.6
15.8
15.6
15.8
15.6
18.9
15.6
18.9
15.6
18.9
15.6
18.9
15.6
22.1
15.6
22.1
15.6
25.2
15.6
22.1
15.6
25.2
15.6
25.2
15.6
25.2
COOLER FLOW
(GPM)
MAX.
1200
1200
1200
1200
1200
1200
1250
1250
1400
1250
1400
1400
1400
COOLER FLOW
(l/s)
MAX.
75.7
75.7
75.7
75.7
75.7
75.7
78.9
78.9
88.3
78.9
88.3
88.3
88.3
FORM 201.21-NM3 (616)
AIR ON CONDENSER (°F)
MIN.
MAX
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
AIR ON CONDENSER (°C)
MIN.
MAX
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
-17.8
51.7
6
43