Unit Setup Mode; Table 19 - Unit Setup Programmable Values - York YCAV0267E Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

MICRO PANEL
Unit Setup Mode will allow the programming all of the
programmable values that the user should never change.
These will either be programmed at the factory or by
service personnel on the job.

TABLE 19 - UNIT SETUP PROGRAMMABLE VALUES

SETUP MODE VALUE
Sys 1 Number of Cond Fans
Sys 2 Number of Cond Fans
Sys 3 Number of Cond Fans
Sys 4 Number of Cond Fans
Compressor 1 Operating hours
Compressor 2 Operating hours
Compressor 3 Operating hours
Compressor 4 Operating hours
Compressor 1 Starts
Compressor 2 Starts
Compressor 3 Starts
Compressor 4 Starts
Clear History Buffers
Remote Temp Reset Option
Remote Current Limit Option
Sound Limit Option
Remote Inputs Service Time
Sys 1 Motor Sensor to Ignore
Sys 2 Motor Sensor to Ignore
Sys 3 Motor Sensor to Ignore
Sys 4 Motor Sensor to Ignore
The following messages will be displayed for the Unit
Setup Mode in the order they appear. The first group
of displays relates to setup parameters that relate to unit
configuration and factory setpoints.
SETUP MODE
◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 1 NUMBER OF COND FANS
SETUP MODE
◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 2 NUMBER OF COND FANS
SETUP MODE
◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 3 NUMBER OF COND FANS
SETUP MODE
◄ DEF XXXXX LO XXXXX HI XXXXX
SYS 4 NUMBER OF COND FANS
308

UNIT SETUP MODE

This mode may be entered by pressing the PROGRAM
key, entering the password 4245, and pressing the √
(ENTER) key. TABLE 19 lists the values that can be
programmed in this mode. Details relating to the actual
message follow the table.
PROGRAMMABLE RANGE
4 to 6
4 to 6
4 to 6
4 to 6
0 to 99,999
0 to 99,999
0 to 99,999
0 to 99,999
0 to 99,999
0 to 99,999
0 to 99,999
0 to 99,999
Yes/ No
Disabled/Enabled
Disabled/Enabled
Disabled/Enabled
5 Min - 60 Min
See Below
See Below
See Below
See Below
SETUP MODE
COMP 1 OPERATING HOURS
SETUP MODE
COMP 2 OPERATING HOURS
SETUP MODE
= X
COMP 3 OPERATING HOURS
SETUP MODE
= X
COMP 4 OPERATING HOURS
= X
= X
FORM 201.21-NM3 (616)
DEFAULT
6
6
6
6
0
0
0
0
0
0
0
0
-
Disabled
Disabled
Disabled
15 Min
None
None
None
None
◄ DEF XXXXX LO XXXXX HI XXXXX
= XXXXX
◄ DEF XXXXX LO XXXXX HI XXXXX
= XXXXX
◄ DEF XXXXX LO XXXXX HI XXXXX
= XXXXX
◄ DEF XXXXX LO XXXXX HI XXXXX
= XXXXX