Water Treatment; Connection Types & Sizes; Cooler Connections; Option Flanges - York YCAV0267E Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

INSTALLATION

WATER TREATMENT

The unit performance provided in the Design Guide
is based on a fouling factor of 0.0001 ft
(0.018m2/hr °C/kW). Dirt, scale, grease and certain
types of water treatment will adversely affect the heat
exchanger surfaces and therefore the unit performance.
Foreign matter in the water system(s) can increase the
heat exchanger pressure drop, reducing the flow rate and
causing potential damage to the heat exchanger tubes.
Aerated, brackish or salt water is not recommended
for use in the water system(s). YORK recommends
that a water treatment specialist should be consulted
to determine whether the proposed water composition
will adversely affect the evaporator materials of carbon
steel and copper. The pH value of the water flowing
through the evaporator must be kept in a range between
7 and 8.5.
PIPEWORK ARRANGEMENT
The following is a suggested piping arrangement for
single unit installations. For multiple unit installations,
each unit should be piped as shown in FIG. 3.
-Isolating Valve - Normally Open
-Isolating Valve - Normally Closed
-Flow Regulating Valve
-Flow Measurement Device
-Strainer
-Pressure Tapping
-Flow Switch
-Flanged Connection
-Pipework
FIG. 3 - PIPEWORK ARRANGEMENT
32
CONNECTION TYPES & SIZES
For connection sizes relevant to individual models refer
hr°F/Btu
to the Technical Data Section.
2

COOLER CONNECTIONS

Standard chilled liquid connections on all coolers are of
the Victaulic Groove type (See FIG. 4).
FIG. 4 - VICTAULIC GROOVE

Option Flanges

One of two types of flanges may be fitted depending
on the customer or local Pressure Vessel Code require-
ments. These are Victaulic-Adapter flanges, normally
supplied loose, or weld flanges, which may be supplied
loose or ready-fitted. Victaulic-Adapter and weld flange
dimensions are to ISO 7005 - NP10.
LD10507
WELD FLANGE
FIG. 5 - FLANGE ATTACHMENT
FORM 201.21-NM3 (616)
LD10494
VICTAULIC ADAPTER
LD10495
JOHNSON CONTROLS