Changing The Rated Voltage Of The Binary-Signal Inputs - Siemens 7UT51 Instruction Manual

Protective relay
Hide thumbs Also See for 7UT51:
Table of Contents

Advertisement

17
Installation and Servicing
17.10
Changing the Rated Voltage of the Binary
A binary-signal input is actuated by applying a control
voltage across its two terminals. When delivered from
the factory, the voltage required to actuate the binary
input is the same as the relay's DC supply power
voltage, which is specified when the relay is ordered. If
appropriate, the actuating-voltage for each
binary-signal input can be independently changed to a
different voltage. The change requires a hardware
modification.
For a rated voltage of 24/48/60V, CONNECT the wire jumper corresponding to the binary
For a rated voltage of 110/125/220/250V, DISCONNECT the wire jumper corresponding to the binary
Main Module (7UT512 and 7UT513):
Binary
Binary
Auxiliary Module (7UT513 only):
-
Binary
Signal Input 3: Wire Jumper X7
-
Binary
Signal Input 4: Wire Jumper X8
-
Binary
Signal Input 5: Wire Jumper X9
Figure 17.17 Locations of Jumpers for Setting Rated Voltage of Binary
192
-
Signal Input 1: Wire Jumper X21
-
Signal Input 2: Wire Jumper X22
1. Remove the module(s) from the relay case as
described in Section XREF.
2. If the last two characters of the relay's serial
number are JH or alphabetically earlier, use a
soldering iron, connect or disconnect the wire
jumpers as shown in Figure 17.17.
or
If the last two characters of the relay's serial
number are KK or alphabetically later, position
the plug jumpers and shown in Figure 17.18
and Figure 17.19.
3. Return the module(s) to the relay case, as
described in Section XREF.
-
Signal Inputs (for Production Series /JH or Earlier).
7UT51 v3
Signal Inputs
-
-
signal input.
-
signal input.
PRIM-2330C