PVD40-500-V-C Surge Diverter
Class II SPD arrester in accordance with IEC
61643-1:2005. Compliance to UL1449 ed.3.
500vdc Surge Protection for PV installations
FEATURES
2 mode protection +ve - Earth, -ve - Earth
Compact solution for solar inverter protection
2 pole wide Din 43880 form factor
Replaceable plug in protection module
Includes floating-contact alarm output
Available in a range of DC voltages to 1000vdc.
Applications
Grid inter active inverters
Standby inverters
SPECIFICATIONS
Manufacturers name and model
Method of mounting
Input voltage
Maximum continuous operating
voltage - MCOV
Service type
Test classification
Supply current
Initial clamp voltage
Maximum rated surge current -
Ismax 8/20us
Nominal surge current –
Inom 8/20us
Residual voltage (Vpl) @ Inom
20kA, 8/20uS at terminals
Nominal surge lifetime (In)
Internal protection
External disconnector
( if required )
Terminations
Alarms/indicators
Location Category
Enclosure rating
Applicable standards.
Dimensions
Weight
Environment
Warranty
Specification are subject to change without notice. Copyright 2009 Eaton Industries Pty Ltd
Eaton PVD40-500-V-C
Din rail mount
450 - 500VDC
530VDC
+VE – E , -VE - E
Class II
<10mA
500VDC
40kA
20kA
1.6kV
20kA (8/20uS), 20 times
MOV thermal disconnect
device.
Gg/Gl HRC fuses, 125A
maximum.
Main terminals multi strand
2
25mm
2
Alarm terminals 1.5mm
Flag indicator, alarm relay
contact 250VAC/24VDC, 2A
Indoor
IP20
IEC61643-1:2005, UL1449
ed.3
90mm (H) x 36mm (W) x
68mm (D). excluding alarm
connector
180g
-10 to 60C, 0-90%RH
12 months, workmanship
and materials
Technical Specification –PVD40-500-V-C
FUNCTIONAL DESCRIPTION
The
PVD40-500-V-C
photovoltaic solar panel inverters from harmful
transients by diverting excess energy to earth from
+ve and –ve conductors to earth.
.
This model (PVD40-500-V-C) is designed for 450-
500vdc systems. If your power system is a
different voltage, this model is NOT suitable.
Please contact your supplier for a suitable model to
suit your application.
OPERATION
The operational status of the unit is shown by a flag
indicator on the front of the unit. In normal operation,
the flag is green. If the unit becomes damaged, the
flag changes to red, indicating that replacement is
necessary. A contact alarm output is fitted to the
base of unit and will change over if the unit is faulty.
WARRANTY
Eaton warrants this unit against faulty parts and
workmanship for a period of 12 months from the date
of purchase. If this product fails to operate correctly,
please contact your Eaton representative. This
warranty doesn't cover neglect or intentional misuse.
As this product is intended for use in electrically
harsh environments no claim is made of suitability for
purpose. This unit is designed to reduce the
likelihood of damage. Please also note that an
excessive surge, such as from a direct lightning strike
to the site or a power system fault, may cause
damage to the unit and render it inoperable. A unit
that has been damaged in this way is not
warrantable.
Page 1 of 2
is
designed
For installation details,
See over page.
to
protect
Tvss Doc# 510092