Tripp Lite SmartOnline SU1500LCD1U Owner's Manual page 22

True on-line single-phase 1u ups systems with pure sine wave output
Table of Contents

Advertisement

Available languages

Available languages

6 Operation
UPS Operating
Voltage
Bypass High Range
Bypass Low Range
Off Mode Setting
For setup procedures, refer to the following:
1. Press the scrolling buttons
2. Press the scrolling button
3. Press the confirmation button for 0.1 second to confirm the parameter. The LCD will go to the next setup item.
4. In Setup Mode, press the scrolling button
5. In Setup Mode, if no buttons are pressed for more than 2 minutes, the LCD will exit Setup Mode and return to the original
display.
Buzzer setup can be performed in all operation modes. Other setup actions can only be configured when the UPS is running in
Off Mode.
Note: Only qualified service personnel can perform setup actions.
for more than 3 seconds to enter Setup Mode.
or
for 0.1 second to change the parameter.
for more than 3 seconds. The LCD will return to the original display.
Selectable Options:
100: Inverter voltage setting to 100V
120: Inverter voltage setting to 120V (Default)
127: Inverter voltage setting to 127V
Selectable Options:
5: Bypass range setting to 5%
10: Bypass range setting to 10% (Default)
15: Bypass range setting to 15%
20: Bypass range setting to 20%
Selectable Options:
5: Bypass range setting to 5%
10: Bypass range setting to 10%
15: Bypass range setting to 15% (Default)
20: Bypass range setting to 20%
Selectable Options:
On: Off Mode setting to bypass output (Default)
Off: Off Mode setting to no output
22