Adjusting The Tv-Uc683T Driver Properties; Driver - Carrier TruVu UC683T Installation And Startup Manual

Table of Contents

Advertisement

Adjusting the TV-UC683T driver properties

After you find and upload the TV-UC683T in the i-Vu® interface, you may want to customize the TV-UC683T's
settings for your applications. You can change settings on the Driver Properties page.
In the i-Vu® interface, right-click the TV-UC683T in the navigation tree and select Driver Properties.
1
Adjust the driver as desired.
2

Driver

The Driver page provides the following information plus the items described in the table below:
The date/time of last parameter change or the last time the database was archived
If control programs, properties, and schedules were successfully stored in memory
Undelivered Alarm Status
TouchScreen Control
TouchScreen Schedule Edit
Enable
Controller Clock
Clock Fail Date and Time
Time Synch Sensitivity
(seconds)
Network Microblocks
BACnet third party
integration points capacity,
integration points requested,
and integration points active
Modbus integration points
capacity and integration
points active
Number of poll retries before
Network Input Microblocks
indicate failure
TruVu™ UC683T
Installation and Start-up Guide
Check this field to allow a user to edit this controller's schedules from an
Equipment Touch or System Touch Schedules screen.
NOTE Schedules edited on an Equipment Touch or System Touch are not
uploaded to the i-Vu® application. This could result in the controller operating on
a schedule that differs from the one you see in the i-Vu® interface.
Date and time the controller uses when its real-time clock is invalid.
When the controller receives a time sync request, if the difference between the
controller's time and the time sync's time is greater than this field's value, the
controller's time is immediately changed. If the difference is less than this field's
value, the controller's time is slowly adjusted until the time is correct.
Shows how many third-party BACnet points the TV-UC683T allows (capacity), how
many points are in the control program (requested), and how many are currently
active (not disabled in i-Vu®).
For example, if the controller allows 400 points, the control program has 350
points, and you disabled 30 points in i-Vu®, you would see:
Integration points capacity: 400
Integration points requested: 350
Integration points active: 320
Shows how many Modbus points the TV-UC683T allows (capacity) and how many
are currently active.
The maximum number of retries after the initial attempt that a Network
microblock will attempt to communicate with its target device. If unsuccessful, the
point will transition to an idle state for 30 seconds before attempting to
communicate again. Change this field only if directed by Technical Support.
33
Adjusting the TV-UC683T driver properties
CARRIER CORPORATION ©2021
All rights reserved