ICP DAS USA LRA-900-E Firmware Update page 7

Hide thumbs Also See for LRA-900-E:
Table of Contents

Advertisement

Step 9:
Power-on reset
the LRA-900-E module in
Step 10:
Confirm that the two MAC addresses (factory-default) listed in the Command Prompt
window,
"Waiting request from MAC x.x.x.x"
same, as indicated in the image below. If these addresses do not match, the update can
not proceed. Refer to
Step 11:
Once the update is complete (i.e., when the progess indicator reaches 100%), set the
Switch"
to
the"Run"
Step 12:
Power-on reset
the LRA-900-E module to operate the module in
Step 13:
In the eSearch Utility, search for the LRA-900-E module again to verify that it is
functioning correctly.
reconfigured after updating the firmware. Refer to
details.
Step 14:
Click the name of the LRA-900-E module to highlight it.
LRA-900-E (Ethernet to LoRa Radio Modem) Firmware Update via Ethernet
Copyright © 2018 ICP DAS Co., Ltd. All Rights Reserved
note4 (Page 21)
below for more details.
position.
Note that the network settings for the module may need to be
"Init Mode"
to initiate the update.
and
"BOOTPREQ from MAC:
Step 3 in Chapter1
E-mail: service@icpdas.com
x.x.x.x",
"Run
Mode".
above for more
Version 1.0.0
are the
"Init
7
Page: