Step 11:
Confirm that the two MAC addresses (factory-default) listed in the Command Prompt
window,
"Waiting request from MAC x.x.x.x"
and
"BOOTPREQ from MAC:
x.x.x.x", are the
same, as indicated in the image below. If these addresses do not match, the update can
not proceed. Refer to
note4 (Page 21)
below for more details.
Step 12:
Once the update is complete (i.e., when the progess indicator reaches 100%), close the
Command Prompt window.
Step 13:
In the eSearch Utility, search for the LRA-900-E module again to verify that it is
functioning correctly.
Note that the network settings for the module may need to be
reconfigured after updating the firmware. Refer to
Step 3 in Chapter1
above for more
details.
Step 14:
Click the name of the LRA-900-E module to highlight it.
Step 15:
Click the
"Web"
button and the default web browser will be opened.
12
LRA-900-E (Ethernet to LoRa Radio Modem) Firmware Update via Ethernet