4.2.2 Troubleshooting 
 
 all soldering work must be carried out by a someone qualified to do so. 
 replacement pipes must always be made of copper in compliance with standard NF EN 12735‐1. 
 leak detection; pressure test: 
- never use oxygen or dry air, risk of fire or explosion,  
- use dry nitrogen or the mixture of nitrogen and refrigerant indicated on the information plate,  
- the test pressure for both the high and low pressure circuits must not exceed 42 bar. 
 the  high  pressure  circuit  pipes  are  made  of  copper  and  have  a  diameter  equal  to  or  greater  than  1''5/8.  A 
certificate as indicated in §2.1 in compliance with standard NF EN 10204 will be requested from the supplier and 
filed in installation technical documentation. 
 technical data relative to the safety requirements of the various applicable directives must be indicated on the 
information plate.  
 This data must be recorded in the installation instructions for the device which are included in the installation 
technical  file:  model,  code,  serial  number,  maximum  and  minimum  OT,  OP,  year  of  manufacture,  EC  label, 
manufacturer's  address,  refrigerant  and  weight,  electrical  parameters,  thermo‐dynamic  and  acoustic 
performances. 
 
4.3 Available accessories 
 
Name 
Representation  
 
4.4 Recycling 
 
This symbol means that your device must not be thrown in the bin. The device must be collected by a 
selective  system  in  view  of  re‐use,  recycling  or  similar.  Any  substances  it  may  contain  which  are 
potentially dangerous to the environment shall be eliminated or neutralised. 
Request information on recycling procedures from your retailer. 
 
5. Troubleshooting 
 
5.1 Display of the regulator 
 
Display 
Designation 
Protection of 
heat exchanger 
 
in cold mode 
temperature 
defect for the 
 
exchanger in 
"cooling" mode 
Phase order 
defect (only on 
three‐phased 
 
 
 
 
 
 
H03620‐00.D2.EN – 2013/03
PAC NET 
Wintering cover 
 
Temperature of ST4 
sensor too low 
High 
Temperature probe ST3 
above 60°C or 
air heat 
evaporator scaled up 
1. wiring incorrect on 
the supply terminal 
board of the device, 
2. modification of phase 
order by electrical 
models) 
supplier, 
3. temporary failure of 
one or several phases 
 
Remote control unit 
 
Cause 
Wait for the surrounding 
temperature to become 
Clean the evaporator, if the 
defect persists, contact an 
approved technician 
1. reverse the phases on the 
supply terminal board 
(without power to the device) 
2, 3, 4. contact your electricity 
provider to find out if 
modifications have been made 
to your equipment. 
 
Technical room kit 
 
Solution 
Automatic 
warmer 
Automatic if 
temperature 
probe ST3 is 
below 45°C 
Switch the 
supply off or 
Reset 
power 
 
press 
10 