3.3 Check separator daily to be sure automatic drain
is discharging.
NOTE: Units with two stage filtration have two sets of drains.
3.4 Blow down separator weekly by pushing test
button on control panel.
3.5 Rebuild drain mechanism annually.
To facilitate service, maintenance kits are available.

SIZING

Determining dryer capacity at actual operating conditions
To determine the maximum inlet flow capacity of a dryer at
various operating conditions, multiply the rated capacity from
Table 1 by the multipliers shown in Table 2.
2
Example: How many scfm can an air-cooled model 1000
handle when compressed air to be dried is at 200 psig and
5
100°F; ambient air temperature is 80°F; and a 45°F dew point
temperature is desired?
Answer: 1,000 x 1.22 x 1.12 x 1.2 = 1,640 scfm.
TABLE 1
Rated capacity (scfm) and pressure drop @ 100 psig inlet
pressure, 100°F inlet temperature, and 100°F ambient tem-
perature
MODEL
Rated capacity
of air-cooled
models (scfm)
TABLE 2
Air capacity correction factors (Multipliers)
INLET
PRESSURES
psig
kgf/cm
50
3.5
80
5.6
100
7.0
125
8.8
150
10.5
1b
175
12.3
200
14.0
COOLING MEDIUM*
AMBIENT
TEMPERATURE
°F
80
90
100
110
*Air-cooled models; water-cooled models use 1.15 multiplier if cooling
water is below 35 ° C, 95 ° F.
1000
1250
1500
60 Hz
1000
1250
1500
50 Hz
840
1050
1250
INLET COMPRESSED AIR CONDITIONS
INLET TEMPERATURES
80°F
90°F
2
27°C
32°C
1.35
1.05
1.50
1.17
1.55
1.23
1.63
1.31
1.70
1.37
1.75
1.42
1.80
1.47
DEWPOINT
MULTIPLIER
TEMPERATURE
°C
°F
27
1.12
38
32
1.06
45
38
1.00
50
43
0.94
1750
2000
2500 3000
1750
2000
2500 3000
1460
1700
2100 2500
100°F
110°F
120°F
38°C
43°C
49°C
0.84
0.69
0.56
0.95
0.79
0.66
1.00
0.82
0.70
1.07
0.91
0.74
1.13
0.95
0.80
1.18
0.99
0.84
1.22
1.03
0.89
OUTLET DEWPOINT
MULTIPLIER
°C
3
1.0
7
1.2
10
1.3
9