Gardner Denver RHP Series Instruction Manual

Gardner Denver RHP Series Instruction Manual

Hide thumbs Also See for RHP Series:

Advertisement

3250997
Rev. D
07/16
INSTRUCTION MANUAL
RHP Series
Models:
RHP130, RHP200, RHP300,
RHP500, RHP750, RHP1000
For Sales and Service: (800) 883-2477
Or visit Sales and Service at www.gardnerdenverproducts.com
HIGH PRESSURE
REFRIGERATED
TYPE
COMPRESSED
AIR DRYERS

Advertisement

Table of Contents
loading

Summary of Contents for Gardner Denver RHP Series

  • Page 1 3250997 Rev. D 07/16 INSTRUCTION MANUAL RHP Series Models: RHP130, RHP200, RHP300, RHP500, RHP750, RHP1000 HIGH PRESSURE REFRIGERATED TYPE COMPRESSED AIR DRYERS For Sales and Service: (800) 883-2477 Or visit Sales and Service at www.gardnerdenverproducts.com...
  • Page 2: Table Of Contents

    CONTENTS GENERAL SAFETY INFORMATION ..................1 RECEIVING, MOVING, AND UNPACKING ................1 1.0 INSTALLATION ......................... 2 1.1 Location ............................2 1.2 Mounting ............................3 1.3 Piping Connections .......................... 3 1.4 Electrical Connections ........................3 1.5 Moisture Separator ........................... 3 2.0 OPERATION ........................4 2.1 Minimum/Maximum Operating Conditions ..................
  • Page 3: General Safety Information

    GENERAL SAFETY INFORMATION RECEIVING, MOVING, AND UNPACKING PRESSURIZED DEVICES: A. RECEIVING This equipment is a pressure containing This shipment has been thoroughly checked, packed and device. inspected before leaving our plant. It was received in good condition by the carrier and was so acknowledged. • Do not exceed maximum operating pressure as shown on equipment Check for Visible Loss or Damage. If this shipment shows serial number tag.
  • Page 4: Installation

    IMPORTANT: READ PRIOR TO STARTING THIS EQUIPMENT 1.0 INSTALLATION 1.1 Location For typical placement in a compressed air system, see drawing. Air compressor intake – Locate air compressor so that Aftercooler contaminants potentially harmful to the dryer (e.g. ammo- Dryer nia) are not drawn into the air system. Compressor Oil Removal Separator...
  • Page 5: Mounting

    1.2 Mounting C. Electrical entry on larger dryers is through a hole in the cabinet. It is located on the right side panel when facing Mount the dryer on a level solid surface. Holes are provided in the front of the unit. Connect power source to terminal the dryer base to permanently mount the dryer to the floor. strip in electrical enclosure as shown on the wiring dia- gram included with the dryer.
  • Page 6: Operation

    2.0 OPERATION If water is present downstream of the dryer, always verify that any condensate drains installed upstream of 2.1 Minimum/Maximum Operating Conditions the dryer are draining properly before attempting to readjust Maximum inlet air pressure: 725 psig (50 barg) the LED setting. Minimum inlet air pressure: 15 psig (1.0 barg) For minimum inlet air pressures that fall between column values, the setting for the lower pressure is recommended.
  • Page 7: Timer Drain Programming Mode

    2.4 Timer Drain Programming Mode Dew Point Drain Interval Temperature Selector Indicator Condensate Draining (Flashes in programming mode) (LED illuminated Drain Interval indicates drain Program cycle setting) 1. Press the “Drain Interval Program” button. The “Conden- sate Draining” LED will start to flash, and the illuminated LED on the “Dew Point Temperature Indicator” will identify the factory setting for “Minutes Between Drain Cycles.” (See Table 1) 2. Press and release the “Drain Interval Selector” button to sequence the “Minutes Between Drain Cycle LED’s” from left to right until reaching your selection. The “Red” LED is not used (Reference Table 2 for “Drain Cycle Intervals”) 3. To initiate the new setting, press the “Drain Interval Pro- gram” button (this will store the new setting and exit the program).
  • Page 8: Maintenance

    3.0 MAINTENANCE f) Remove and replace complete element. 1) Unscrew the old filter element and discard. 3.1 Daily Also, discard the small O-ring that seals the filter Check separator daily to be sure automatic drain is dis- to the filter assembly head. charging. g) Install new filter element and bowl with new O-rings properly seated to head or bowl (dependent upon 3.2 Weekly dryer size). Blow down separator weekly by pushing test button on h) Connect drain line and replace panel.
  • Page 9: Troubleshooting Guide

    4.0 TROUBLESHOOTING GUIDE SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION A) Water downstream of dryer 1. Residual free moisture remaining in Blow out system with dry air downstream pipelines 2. Air bypass system is open Check valve positions 3. Inlet and Outlet connections are reversed Check for correct connection 4.
  • Page 10: Reference

    5.0 REFERENCE 5.1 Sizing Determining dryer capacity at actual operating conditions To determine the maximum inlet flow capacity of a dryer at vari- ous operating conditions, multiply the rated capacity from Table 1 by the multipliers shown in Table 2. Example: How many scfm can an air-cooled model RHP300 handle when compressed air to be dried is at 350 psig and 90°F;...
  • Page 11: Engineering Data

    5.2 Engineering Data Models RHP130 RHP200 RHP300 RHP500 RHP750 RHP1000 Air System Data Maximum / Minimum Inlet Air Pressure (compressed air at inlet to dryer) 725 psig (50 barg) / 15 psig (1.0 barg) Maximum / Minimum Inlet Air Temperature (compressed air at inlet to dryer) 120°F (49°C) / 40°F (4°C) Maximum / Minimum Ambient Temperature Air-cooled: 110°F (43°C) / 40°F (4°C), Water-cooled: 130°F (54°C) / 40°F (4°C)
  • Page 12: Dimensions / Weights

    6.0 DIMENSIONS / WEIGHTS Dimensions, inches (mm) Model RHP130 RHP200 RHP300 RHP500 RHP750 RHP1000 37.56 (954) 37.56 (954) 38.60 (980) 38.60 (980) 58.06 (1475) 58.06 (1475) 25.62 (651) 25.62 (651) 32.15 (817) 32.15 (817) 32.15 (817) 32.15 (817) 2.50 (63.5) 2.50 (63.5) 2.50 (63.5) 2.50 (63.5)
  • Page 13: Drawings

    7.0 DRAWINGS 7.1 Process Gas / Refrigeration Flow Diagram: Models RHP130 and RHP200...
  • Page 14: Process Gas / Refrigeration Flow Diagram: Models Rhp300 Through Rhp1000

    7.2 Process Gas / Refrigeration Flow Diagram: Models RHP300 through RHP1000...
  • Page 15: Wiring Diagram: Models Rhp130 And Rhp200 (115 Or 208-230V/60 Hz, 100 Or 240V/50 Hz)

    7.3 Wiring Diagram: Models RHP130 and RHP200 (115 or 208-230V/60 Hz, 100 or 240V/50 Hz)
  • Page 16: Wiring Diagram: Models Rhp300 Through Rhp750 (230-400-460V/3/50-60 Hz)

    7.4 Wiring Diagram: Models RHP300 through RHP750 (230-400-460V/3/50-60 Hz) (Page 1 of 2)
  • Page 17 Wiring Diagram: Models RHP300 through RHP750 (230-400-460V/3/50-60 Hz) (Page 2 of 2)
  • Page 18: Wiring Diagram: Model Rhp1000 (230-400-460V/3/50-60 Hz)

    7.5 Wiring Diagram: Model RHP1000 (230-400-460V/3/50-60 Hz) (Page 1 of 2)
  • Page 19 Wiring Diagram: Model RHP1000 (230-400-460V/3/50-60 Hz) (Page 2 of 2)
  • Page 20: Wiring Diagram: Models Rhp300 Through Rhp1000 (575-460/3/60 Transformer Pack)

    7.6 Wiring Diagram: Models RHP300 through RHP1000 (575-460/3/60 Transformer Pack)
  • Page 21: Replacement Parts List

    8.0 REPLACEMENT PARTS LIST 8.1 Replacement Parts RHP130 RHP200 115/1/60 115/1/60 PARTS DESCRIPTION 208-230/1/60 220-240/1/50 208-230/1/60 220-240/1/50 100/1/60 100/1/60 Condensing Unit Assembly G5002001 G5002002 G5002003 G7427771 G7427772 G7427773 Compressor (Only) G5002243 G5002250 G5002256 G7427777 G7427778 G7427779 Overload G5002244 G5002251 G5002257 G3233219 G3233220 G3252935...
  • Page 24: Warranty

    For additional information contact you local representative or Gardner Denver Inc. 1800 Gardner Expressway, Quincy, IL 62305 Telephone: (800) 682-9868 FAX: (217) 224-7814 Visit our Web Site: www.gardnerdenver.com © 2016 Gardner Denver, Inc. Printed in U.S.A 3250997 Rev. D 07/16 RHP130-1000 New Platform 1st Edition...

This manual is also suitable for:

Rhp130Rhp200Rhp300Rhp500Rhp750Rhp1000