Carrier N92ESN Installation, Start-Up, Operating And Service And Maintenance Instructions page 53

Single-stage, 35-in. (889 mm) tall, 4-way multipoise high efficiency condensing gas furnace
Table of Contents

Advertisement

N92ESN: Installation, Start-up, Operating and Service and Maintenance Instructions
FURNACE
SPEED
SIZE
TAPS
5, 6
Gray
Yellow
0802120
Blue
Orange
3
Red
5, 6
Gray
Blue
Yellow
1002120
3
Orange
3
Red
5, 6
Gray
5, 6
Yellow
1002122
Orange
Blue
3
Red
5, 6
Gray
Blue
3
1202420
Yellow
3
Orange
3
Red
See NOTES following table.
1. A filter is required for each return-air inlet. Airflow performance includes a 3/4-in. (19 mm) washable filter media such as contained in a factory-authorized filter rack. See accessory list
in Specification Sheet. To determine airflow performance without this filter, assume an additional 0.1 in. w.c. available external static pressure.
2. ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.
3. The "Function" column identifies which speed taps can be used for heating. Shaded areas indicate that this airflow range is BELOW THE RANGE ALLOWED FOR HEATING
OPERATION. THESE AIRFLOW RANGES MAY ONLY BE USED FOR COOLING.
4. If the same motor speed tap is needed for heating and cooling, a Jumper Wire accessory kit is available, see Specification Sheet for the current Jumper Wire accessory part number.
Reference the "Start-up, Adjustments, and Safety Check" section for further Jumper Wire instructions.
5. Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return. A minimum filter size of 20" x 25" (508 x 635 mm) is required.
6. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
7. The "-" entry indicates an unstable operating condition.
Adjust Cooling Airflow
The cooling airflow can be set from the remaining blower speed taps.
Refer to the Air Delivery Tables in these instructions.
If the same motor speed tap is needed for heating and cooling, a Jumper
Wire accessory kit is available, see Specification Sheet for the current
Jumper Wire accessory part number. The single wire end of the jumper
will be connected to the desired blower motor speed lead. The two wire
end of the jumper will be connected to the control board, connecting one
wire to the HEAT (heating blower tap) terminal and the other will be
connected to the COOL (cooling blower tap). Use the provided wire ties
to secure the loose blower motor speed lead and any other loose wires,
being careful not to put tension on any wire connectors.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
CAUTION
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the
rating plate. Recommended operation is at the mid-point of rise range
or slightly above.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 21 – Air Delivery - CFM (With Filter) (Continued)
Function
Cooling. Do not use for heating
Alt Cooling or alt Heating
Heating or alt Cooling
Alt Cooling or alt Heating
Alt Cooling. Do not use for heating
Cooling. Do not use for heating
Heating or alt Cooling
Alt Cooling or alt Heating
Alt Cooling or alt Heating
Alt Cooling. Do not use for heating
Cooling. Do not use for heating.
Alt Cooling. Do not use for heating.
Alt Cooling or alt Heating
Heating or alt Cooling
Alt Cooling or alt Heating
Cooling. Do not use for heating
Heating or alt Cooling
Alt Cooling or alt Heating
Alt Cooling. Do not use for heating
Alt Cooling. Do not use for heating
EXTERNAL STATIC PRESSURE (IN.W.C.)
0.10
0.20
0.30
0.40
2020 1965 1920 1865 1815 1760 1705 1650 1595 1545
1650 1590 1535 1475 1425 1370 1315 1260 1205 1145
1495 1430 1365 1310 1260 1200 1145 1085 1030
1420 1355 1290 1235 1175 1120 1060 1005
1200 1120 1060
995
2060 2010 1955 1905 1850 1800 1750 1690 1630 1565
1730 1675 1620 1565 1510 1455 1385 1325 1270 1210
1685 1630 1570 1515 1460 1410 1345 1280 1225 1170
1445 1370 1310 1250 1185
1235 1155 1090 1020
2205 2160 2120 2085 2045 2005 1965 1925 1885 1840
2120 2080 2035 1995 1955 1915 1875 1830 1790 1745
1800 1755 1710 1665 1615 1570 1520 1470 1420 1375
1680 1630 1580 1535 1485 1435 1380 1330 1275 1225
1500 1445 1390 1340 1285 1225 1170
2070 2020 1965 1910 1850 1790 1725 1660 1605 1550
1795 1735 1680 1620 1560 1495 1440 1375 1315 1255
1465 1400 1340 1270 1210 1150 1090 1030
1295 1235 1165 1095 1030
1095 1020
945
875
Adjust Thermostat Heat Anticipator
Mechanical thermostat: Set thermostat heat anticipator to match the
amp draw of the electrical components in the R-W circuit. Accurate amp
draw readings can be obtained at the wires normally connected to
thermostat subbase terminals R and W. The thermostat anticipator
should NOT be in the circuit while measuring current.
1. Remove thermostat from subbase or from wall.
2. Connect an amp meter across the R and W subbase terminals or R
and W wires at wall. See
3. Record amp draw across terminals when furnace is in low heat and
after blower starts.
4. Set heat anticipator on thermostat per thermostat instructions and
install on subbase or wall.
5. Install blower access door.
Electronic thermostat: Set cycle rate for 3 cycles per hr.
10 TURNS
5.0 AMPS ON AMMETER
EXAMPLE:
10 TURNS AROUND JAWS
Fig. 64 – Amp. Draw Check with Ammeter
53
0.50
0.60
0.70
0.80
0.90
945
940
875
810
750
685
1115 1055 1005
950
945
900
835
755
690
1110 1055 1000
950
970
905
825
760
805
730
660
585
525
Fig.
64.
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
R
Y W
G
FROM UNIT 24-V
CONTROL TERMINALS
= 0.5 AMPS FOR THERMOSTAT
ANTICIPATOR SETTING
1.00
970
890
625
875
635
880
700
465
A96316

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents