Panasonic WH-MHF12G9E8 Service Manual page 96

(mono bloc) air-to-water heat pump system
Hide thumbs Also See for WH-MHF12G9E8:
Table of Contents

Advertisement

16.5.8 Outdoor Low Pressure Abnormality (H63)
Malfunction Decision Conditions:
During operation of heating, when the outdoor low pressure sensor output signal is 0Vdc or 5Vdc.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty sensor.
3
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 4 times in 20 minutes.