Panasonic WH-MHF12G9E8 Service Manual page 42

(mono bloc) air-to-water heat pump system
Hide thumbs Also See for WH-MHF12G9E8:
Table of Contents

Advertisement

11.4.2 Connecting Requirement
For model WH-MHF09G3E8:
The equipment's power supply 1 complies with IEC/EN 61000-3-2.
The equipment's power supply 1 complies with IEC/EN 61000-3-3 and can be connected to current supply
network.
The equipment's power supply 2 complies with IEC/EN 61000-3-2.
The equipment's power supply 2 complies with IEC/EN 61000-3-3 and can be connected to current supply
network.
For model WH-MHF12G9E8:
The equipment's power supply 1 complies with IEC/EN 61000-3-2.
The equipment's power supply 1 complies with IEC/EN 61000-3-3 and can be connected to current supply
network.
The equipment's power supply 2 complies with IEC/EN 61000-3-2.
The equipment's power supply 2 complies with IEC/EN 61000-3-11 and shall be connected to suitable supply
network, with the following maximum permissible system impedance Z
Please liaise with supply authority to ensure that the power supply 2 is connected only to a supply of that
impedance or less.
11.4.3 Wired Remote Control Installation
Do not modify the length of the remote control cable. Otherwise, it will cause fire or electrical shock.
Be sure to turn off the main power before installing and connecting the remote control. Otherwise, it will cause the electrical shock.
Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, fire or electrical shock.
If passing the remote control cable through a wall, be sure to install a water trap above the cable. Otherwise, it will cause the
electrical shock.
Install in a flat surface to avoid warping of remote control, else damage to the LCD case or operation problems may result.
Avoid installing the remote control cable near refrigerant pipes or water pipes, else will cause electrical shock or fire.
Install the remote control cable at least 5 cm away from electric wires of other appliances to avoid miss operation (electromagnetic
noise).
Be sure to use only the accessory screws to avoid damage of remote control PCB.
Attached Accessories
No.
Name
(1)
Remote control
(2)
Remote control cable
Screw
(3)
(M4 machine pitched - 30 mm)
Screw
(4)
(M4 self-tapping - 14 mm)
WARNING
CAUTION
Qty.
Diagram
1
1
3
3
42
= 0.449Ω per phase at the interface.
max
Remark
Length (15 m)
Installing the remote control to an outlet box
(embedded cable)
Installing the remote control to the wall
(exposed cable)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-mhf09g3e8

Table of Contents