Panasonic WH-MHF12G9E8 Service Manual page 107

(mono bloc) air-to-water heat pump system
Hide thumbs Also See for WH-MHF12G9E8:
Table of Contents

Advertisement

16.5.19 Compressor Rotation Failure (F14)
Malfunction Decision Conditions:
A compressor rotation failure is detected by checking the compressor running condition through the position
detection circuit.
Malfunction Caused:
1
Compressor terminal disconnect.
2
Faulty outdoor unit PCB (main).
3
Faulty compressor.
Abnormality Judgment:
Continue 4 times in 20 minutes.