Trusted TMR 120 Vac Digital Output Module – 16
Channel
Product Overview
The Trusted® 120 Vac Digital Output Module interfaces to 16 field devices. Triplicated diagnostic
tests are performed throughout the Module including measurements for current and voltage on
each portion of the voted output channel. Tests are also performed for stuck on and stuck off
failures. Fault tolerance is achieved through a Triple Modular Redundant (TMR) architecture within
the System Side and Quad Element redundancy for each of the 16 output channel circuits.
The Module provides on-board Sequence of Events (SOE) reporting with a resolution of 1 ms. An
output change of state triggers an SOE entry. Output states are automatically determined by
multiple voltage and current measurements for each of the 16 channels of the Module.
Features:
• Triplicated TMR system architecture, with fault tolerant output switching.
• 16 Output Channels: 120 Vac, 0.5 A per channel, field powered as two groups of 8.
• Comprehensive, automatic diagnostics and self-test.
• Short circuit monitoring per channel when energized (requires regular proof testing for
safety related normally de-energized outputs, e.g. F&G).
• Open circuit monitoring when energized or de-energized
• 2500 V impulse withstand opto/galvanic isolation barrier.
• Automatic channel over-current protection, no fuses required.
• On-board Sequence of Events (SOE) reporting with 1 ms resolution.
• Module can be hot-replaced on-line using dedicated 'Companion Slot' (adjacent slot) or
SmartSlot (one spare slot for many Modules) configurations.
• Front Panel output status Light Emitting Diodes (LEDs) for each channel indicate output
status and field wiring faults.
Rockwell Automation Publication ICSTT-RM283H-EN-E
Issue 15
Trusted

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation Trusted TMR 120

  • Page 1 ICSTT-RM283H-EN-E (PD-T8472) Trusted Trusted TMR 120 Vac Digital Output Module – 16 Channel Product Overview The Trusted® 120 Vac Digital Output Module interfaces to 16 field devices. Triplicated diagnostic tests are performed throughout the Module including measurements for current and voltage on each portion of the voted output channel.
  • Page 2 Trusted ICSTT-RM283H-EN-E • Front Panel Module status LEDs indicate Module health and operational mode (Active, Standby, Educated). • TϋV Certified IEC 61508, SIL 3. Rockwell Automation Publication ICSTT-RM283H-EN-E Issue 15...
  • Page 3 PREFACE PREFACE In no event will Rockwell Automation be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples given in this manual are included solely for illustrative purposes. Because of the many variables and requirements related to any particular installation, Rockwell Automation does not assume responsibility or reliability for actual use based on the examples and diagrams.
  • Page 4 PREFACE Trusted TMR 120 Vac Digital Output Module – 16 Channel IMPORTANT A login is required to access the link. If you do not have an account then you can create one using the "Sign Up" link at the top right of the web page.
  • Page 5 Trusted TMR 120 Vac Digital Output Module – 16 Channel PREFACE SCOPE This manual specifies the maintenance requirements and describes the procedures to assist troubleshooting and maintenance of a Trusted system. WHO SHOULD USE THIS MANUAL This manual is for plant maintenance personnel who are experienced in the operation and maintenance of electronic equipment and are trained to work with safety systems.
  • Page 6 PREFACE Trusted TMR 120 Vac Digital Output Module – 16 Channel WARNINGS AND CAUTIONS WARNING: EXPLOSION RISK Do not connect or disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations or equivalent AVERTISSEMENT - RISQUE D’EXPLOSION...
  • Page 7 Trusted TMR 120 Vac Digital Output Module – 16 Channel PREFACE ISSUE RECORD Issue Date Comments No issue record in source Aug 15 Rebranded and reformatted with correction to Relative Humidity Range and Operating Temperature statements in the Specification Sections,...
  • Page 8 PREFACE Trusted TMR 120 Vac Digital Output Module – 16 Channel Page intentionally left blank Issue 15 Rockwell Automation Publication ICSTT-RM283H-EN-E...
  • Page 9: Table Of Contents

    Trusted TMR 120 Vac Digital Output Module – 16 Channel Table of Contents Table of Contents Description ......................3 1.1. Field Termination Unit (FTU) ....................... 4 1.2. Field Interface Unit (FIU) ......................5 1.3. Host Interface Unit (HIU) ......................6 1.4.
  • Page 10 Table of Contents Trusted TMR 120 Vac Digital Output Module – 16 Channel Fault Finding and Maintenance ................29 5.1. Fault Reporting .......................... 29 5.2. Field Wiring Faults ........................29 5.3. Module Faults ........................... 29 5.4. Companion Slot ......................... 30 5.5.
  • Page 11: Description

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 1. Description 1. Description The TMR 120 Vac Digital Output Module is a member of the Trusted range of Input/Output (I/O) Modules. All Trusted I/O Modules share common functionality and form. At the most general level, all I/O Modules interface to the Inter-Module Bus (IMB) which provides power and allows communication with the TMR Processor.
  • Page 12: Field Termination Unit (Ftu)

    1. Description Trusted TMR 120 Vac Digital Output Module – 16 Channel Figure 1 Module Architecture This High Integrity I/O Module comprises 4 printed circuit boards (PCBs): Host Interface Unit (HIU), the Field Interface Unit (FIU), the Field Termination Unit (FTU), and the Front Panel Unit (or FPU).
  • Page 13: Field Interface Unit (Fiu)

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 1. Description When installed in a Chassis, the FTU Field Connector accepts the Field I/O Cable Assembly attached at the rear of the Chassis. 1.2. Field Interface Unit (FIU) The Field Interface Unit (FIU) is the section of the Module that contains the specific circuits necessary to interface to the particular types of field I/O signals.
  • Page 14: Host Interface Unit (Hiu)

    1. Description Trusted TMR 120 Vac Digital Output Module – 16 Channel Isolation – The FIU provides galvanic isolation between logic and field. The majority voting carried out in the FIU verifies that any single slice failure in the HIU does not degrade the output switch operation.
  • Page 15: Line Monitoring And Output States

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 1. Description bi-colour LEDs provide status indication for the individual I/O signals. Serial data interfaces connect the FPU to each of the HIU slices to control the LED status indicators and monitor the module removal switches 1.5.
  • Page 16: Sequence Of Events Characteristics

    1. Description Trusted TMR 120 Vac Digital Output Module – 16 Channel Module replacement activities depend on the type of spare Module configuration chosen when the system was configured and installed. The Module may be configured with a dedicated Companion Slot or may use a separate SmartSlot. The I/O Module contains extensive fault detection and integrity testing.
  • Page 17 Trusted TMR 120 Vac Digital Output Module – 16 Channel 1. Description Due to the majority voting scheme incorporated on FIU-QA, QB, QC and QD voters, any single HIU main slice A, B or C, failure will not result in the loss of any switch element operation.
  • Page 18 1. Description Trusted TMR 120 Vac Digital Output Module – 16 Channel Page intentionally left blank Issue 15 Rockwell Automation Publication ICSTT-RM283H-EN-E...
  • Page 19: Installation

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 2. Installation 2. Installation 2.1. Module Insertion and Removal CAUTION: The Module contains static sensitive parts. Static handling precautions must be observed. Specifically ensure that exposed connector pins are not touched. Under no circumstances should the Module housing be removed.
  • Page 20: Cable Impedance

    2. Installation Trusted TMR 120 Vac Digital Output Module – 16 Channel 2.2.1. Cable Impedance Custom length multi-core FTA cables are 0.5 mm with a resistance of 40 Ω/km. eg a 50 m cable will have 4 Ω loop impedance at 0.5 A, this equates to a 2 Vdc volt drop.
  • Page 21: Trusted Module Polarisation / Keying

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 2. Installation Table 2 Field Connector Pin-Out 2.5. Trusted Module Polarisation / Keying Due to the high voltages used by the T8472 AC DO Module it differs from other I/O Modules.
  • Page 22 2. Installation Trusted TMR 120 Vac Digital Output Module – 16 Channel For Companion Slot installations both keying strips must be polarized. For this Module (T8472) remove keying pins 1, 5 and 9. Issue 15 Rockwell Automation Publication ICSTT-RM283H-EN-E...
  • Page 23: Application

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 3. Application 3. Application 3.1. Module Configuration There is no configuration required to the physical Output Module. All configurable characteristics of the Module are performed using tools on the Engineering Workstation (EWS) and become part of the application or System.INI file that is loaded into the TMR...
  • Page 24: Rack 1: Do

    3. Application Trusted TMR 120 Vac Digital Output Module – 16 Channel Rack I/O Board Description Data Type Direction No. of Channels DISCREP Channel Discrepancy Integer HKEEPING Housekeeping Registers Integer INFO I/O Module Information Integer Table 3 Complex Equipment Definition There are two OEM parameters included in the first rack (DO Board).
  • Page 25: Rack 2: State

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 3. Application Table 5 Rack 1: DO Descriptions The user application should set the output control signal to true (logic ‘1’) to turn ON or energize an output, and false (logic ‘0’) to turn OFF or de-energize an output.
  • Page 26: Rack 3: Ai - Channel Field Voltage

    3. Application Trusted TMR 120 Vac Digital Output Module – 16 Channel 3.2.3. Rack 3: AI - Channel Field Voltage The AI board returns the field loop voltage at the output. Channel Description Field output channel 1 voltage Field output channel 2 voltage...
  • Page 27: Rack 5: Line_Flt

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 3. Application The IEC 61131 TOOLSET conversion tables may be used to convert the value to engineering units, in this case current. The full-scale range for this number format is decimal ±32, corresponding to physical range –32000 to +32000.
  • Page 28 3. Application Trusted TMR 120 Vac Digital Output Module – 16 Channel Description Channel Units (Full Scale Range) Internal supply current (post regulator) -32768 32767 Output voltage (post isolation) -32768 32767 24V1 Output Voltage -32768 32767 HIU Board Temperature -32768...
  • Page 29 Trusted TMR 120 Vac Digital Output Module – 16 Channel 3. Application Description Channel Units (Full Scale Range) FIU Board Temperature, Output Group 1 Peak -32768 32767 FIU Board Temperature, Output Group 1Peak Channel -32768 32767 FIU Board Temperature, Output Group 2 Average...
  • Page 30: Rack 8: Info

    3. Application Trusted TMR 120 Vac Digital Output Module – 16 Channel 3.2.8. Rack 8: INFO Channel Description Active Module chassis number Active Module slot number Active Module healthy Active Module mode Standby Module chassis number Standby Module slot number...
  • Page 31: Sequence Of Events Configuration

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 3. Application Value Module Mode Shutdown Maintain Active Standby Configuration Unknown, no module present Table 14 Rack 8: INFO bit Descriptions The FCR Status channel reports the fault status of the Active and Standby Modules. The...
  • Page 32: System.ini File Configuration

    3. Application Trusted TMR 120 Vac Digital Output Module – 16 Channel During operation, the Output Module automatically reports time-stamped change of state information for the output data. The TMR Processor automatically logs change of state for configured SOE variables into the system SOE Log. The SOE Log can be monitored and retrieved using the SOE and Process Historian Package running on the EWS.
  • Page 33: Operation

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 4. Operation 4. Operation 4.1. Front Panel Indications Status indicators on the Front Panel of the Module provide visual indications of the Module’s operational status and field output status. Each indicator is a bi-color LED. Located at the top and bottom of each Module is an ejector lever that is used to remove the Module from the Chassis.
  • Page 34: Module Status Leds

    4. Operation Trusted TMR 120 Vac Digital Output Module – 16 Channel 4.2. Module Status LEDs There are six Module status indicators on the Module Front Panel: three Healthy, one Active, one Standby, and one Educated. The Healthy indicators are controlled directly by each Module slice.
  • Page 35: I/O Status Leds

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 4. Operation Indicator State Description Educated Module is not educated. Green Module is educated. Green – flashing Module is recognized by the Processor but education is not complete. Amber - Flashing Active/Standby changeover in progress.
  • Page 36 4. Operation Trusted TMR 120 Vac Digital Output Module – 16 Channel Page intentionally left blank Issue 15 Rockwell Automation Publication ICSTT-RM283H-EN-E...
  • Page 37: Fault Finding And Maintenance

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 5. Fault Finding and Maintenance 5. Fault Finding and Maintenance 5.1. Fault Reporting Output Module faults are reported to the user through visual indicators on the Front Panel of the Module and through status variables which may be automatically monitored in the application programs and external system communications interfaces.
  • Page 38: Companion Slot

    5. Fault Finding and Maintenance Trusted TMR 120 Vac Digital Output Module – 16 Channel Module replacement activities depend on the type of spare Module configuration chosen when the system was configured and installed. The Module may be configured with a Dedicated ‘Companion’...
  • Page 39: Active And Standby Transfers

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 5. Fault Finding and Maintenance If an I/O Module is inserted into a functional system slot which previously had no Active module (e.g. removing and re-inserting as above), then the Processor will educate the Module once it has booted.
  • Page 40 5. Fault Finding and Maintenance Trusted TMR 120 Vac Digital Output Module – 16 Channel I/O Module with the same configuration information as the currently Active I/O Module and place the Standby I/O Module into the Standby state. The Active Module is then placed in the Maintain state (which suspends field loop testing), and any Module specific changeover data is transferred.
  • Page 41: Specifications

    Trusted TMR 120 Vac Digital Output Module – 16 Channel 6. Specifications 6. Specifications System Supply Voltage Range 20 Vdc to 32 Vdc Circuit Type Fault tolerant, fully triplicated with quad output switch circuits. Number of Outputs 16 Channels Independent Power Groups...
  • Page 42 6. Specifications Trusted TMR 120 Vac Digital Output Module – 16 Channel Output Short Circuit Protection Electronic Output Turn-on/off Delay 1.5 AC cycle max. (zero crossing) Channel Monitor Update Every 16 AC cycles Sequence of Events Event Resolution 1 ms...