Greenheck ERCH Installation, Operation And Maintenance Manual page 10

Energy recovery ventilator with heating and cooling
Table of Contents

Advertisement

Unit Installation
Service Clearances / Access Panel - Water-Source Heat Pump
Units require minimum clearances for access on all sides for routine maintenance. Filter replacement, drain pan
inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and belt adjustment are examples
of routine maintenance that must be performed. Blower and motor assemblies, energy recovery wheel cassette, coil
and filter sections are always provided with a service door or panel for proper component access.
*Cassette removal only available
on housing sizes 20 and 45.
B
ACCESS DOOR
OUTDOOR
WEATHERHOOD
Drawing shows optional hot gas reheat coil.
10
Energy Recovery Ventilator with Heating and Cooling
General Description - NOT model specific
EXHAUST AIR
WEATHERHOOD
ACCESS PANEL
A
ACCESS PANEL
ELECTRICAL BOX
HEAT PUMP
36 inches
Model
A (in.)
B (in.)
ERCH-20
48
36
ERCH-45
64
42
ERCH-55
42
42
ERCH-90
42
48
ACCESS DOOR
42 inches
®

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Erch-20Erch-45Erch-55Erch-90