Installing Conduits

Before connecting the inverter, install all conduits in the following order.
To install a conduit:
 1. Switch the DC Safety Switch to OFF.
 2. Release the four Allen screws of the Connection Unit cover and remove the cover.
CAUTION!
When removing the cover, make sure not to damage internal
components. SolarEdge will not be held responsible for any components
damaged as a result of incautious cover removal.
 3. Install a conduit of the required diameter:
To install a 1" conduit, remove the conduit plug together with the reducing
washer.
To install a 3/4" conduit, use the supplied reducing washer.
To install a smaller conduit, use a reducing washer of an appropriate size (not
supplied)
Single Phase Energy Hub Inverter with Prism Technology MAN-01-00842-1.3