Command: 301 Liquid Sensor Status Report - Omntec PROTEUS OEL8000III Series Manual

Table of Contents

Advertisement

OEL8000III Series Models K/X

Command: 301 Liquid Sensor Status Report

Command Format:
Display: <SOH>I301SS
Computer: <SOH>i301SS
Typical Response Message, Display Format:
<SOH>
I10200
JUL 29, 2013
12:00 AM
OMNTEC MFG.
1993 POND ROAD
RONKONKOMA NEW YORK 11779
631-981-2001
LIQUID SENSOR STATUS REPORT
SENSOR LOCATION
1
Tank 0, TANK SUMP12345
2
Tank 1, HiHi_LoLo: 1
3
Tank 1, EmHi_EmLo: 1
4
Tank 1, Low_LoLo: 1
5
Tank 1, Low_EmLo: 1
6
Tank 1, Caut_Low: 1
<ETX>
Typical Response Message, Computer Format:
<SOH>i301SSYYMMDDHHmmSSssss...
Notes:
1. YYMMDDHHmm - Current Date and Time
2. SS - Sensor Number (Decimal, 00 = all)
3. ssss - Sensor Status Value:
0000 = Sensor Normal
0002 = Sensor Fuel Alarm
0005 = Sensor Water Alarm
0006 = Sensor Water Out Alarm
0007 = Sensor High Liquid Alarm
0008 = Sensor Low Liquid Alarm
0016 = LIQUID ALARM
0017 = VAPORS DETECTED
0018 = LEVEL ALARM
0019 = NO REPLY
0020 = BUS NO REPLY
0021 = LOW TEMP ALARM
0022 = HIGH TEMP ALARM
0023 = High Level Alarm
0024 = High/High Level Alarm
0025 = Em_High Level Alarm
SSssss&&CCCC<ETX>
OMNTEC Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 42 of 71 Rev Date: 10-15-2021
STATUS
Normal
Normal
Normal
Normal
Normal
Normal
PROTEUS