UTICA BOILERS STARFIRE IV STEAM 4 Series Installation, Operation & Maintenance Manual page 17

Oil-fired cast iron boiler
Table of Contents

Advertisement

Start-Up And Adjustment Of Oil Burner
(See oil burner instructions for nozzle and electrode setting)
Do not set fire visually.
Instruments are only reliable method to determine proper
air adjustments.
Improperly adjusted burner causes soot and high fuel bills
because of incomplete combustion of the fuel oil. This may
then require excessive boiler maintenance, service costs,
and in some instances, house cleaning or redecorating.
Consult a qualified service mechanic to make proper
adjustments with smoke tester, CO
gauge. Bacharach or Dwyer test kits include these
instruments.
1.
Check oil burner nozzle to verify it is tight in adapter.
Burner mounting bolts should be tight.
BOILER
NO.
SFE-3090
SFE-4125
SFE-5185
SFE-6210
* Boiler model number on rating plate includes suffix 'S' or 'ST'.
IMPORTANT: Check safety control circuit after burner adjustments have been made for satisfactory performance.
OPERATING INSTRUCTIONS
indicator, and draft
2
BECKETT AFG SETTINGS
HEAD
HEAD
STATIC
TYPE
SETTING
L1
--
V1
0
F12
--
F16
--
2.
Check electrode setting, they may have been jarred out
of position during transportation.
3.
Lubricate burner motor if necessary.
4.
Set room thermostat to call for heat, or jump
thermostat contacts on boiler control.
5.
Open all oil line valves.
6.
Turn service switch on. Burner should start.
7.
On one pipe fuel systems only, bleed pump as soon as
burner starts. Allow oil to run until all traces of air in
suction line disappear.
8.
Turn "OFF" burner and install pressure gauge port on
pump.
9.
Start burner again and check oil pressure for 140 lbs.
Adjust if necessary.
NOZZLE
PLATE
3⅜
0.75-60°B
1.10-60°B
1.50-70°B
1.75-70°B
--
17
PUMP
AIR
PRESSURE
BAND
[PSI]
150
1
140
1
150
2
145
2
AIR
SHUTTER
3
8
10
10