Note On Dc Wiring And The Nec; Remote Shutdown Switch Connections (If Equipped) - Generac Power Systems PWRcell M3 Installation Manual

Hide thumbs Also See for PWRcell M3:
Table of Contents

Advertisement

To install REbus wiring:
1. See
4-9. Install REbus conductors to their
Figure
terminal blocks: RE+ to red (A), RE- to blue (B).
2. Install equipment grounding conductor to green ter-
minal block (C).
3. If required, route field wiring conductors through
the grommet wiring chase baffle (D).
NOTE: Do not route wires around the baffle.
4. At the PWRcell Inverter, install RE+ and RE- con-
ductors to any unused 30A REbus DC disconnect.
5. Secure equipment grounding conductor to the
PWRcell Inverter ground bar.
Figure 4-9. REbus Wiring

Note on DC Wiring and the NEC

Some electricians or installers may be unfamiliar with DC
wiring in a residential setting. Note the following:
NEC 215.12(C)(2) for correct DC wiring coloring.
NEC 210.5(C)(2) for identification of DC conduc-
tors carrying more than 50V.
Always adhere to applicable codes when marking and
installing DC conductors.
See
Table
4-2. For all REbus DC wiring observe the fol-
lowing coloring convention:
Table 4-2.
REbus DC Wiring Coloring Convention
Wire
REbus + (RE+)
REbus - (RE-)
Ground (GND)
NOTE: Mark or flag all conductors as appropriate.
Installation Manual for Generac PWRcell Battery
A
B
C
D
009928
Color
Red
Black or Blue with Black Sleeving
Green
Remote Shutdown Switch Connec-
tions (If equipped)
NOTE: See
Figure
4-10. The STOP terminals ship with
a 14 AWG jumper (A) installed. Remove this jumper
before installing an external shutdown switch.
+ STOP -
POWER SEARCH
DISCONNECT "OFF"
AND DE-ENERGIZE
A
REMOVE
FOR
REMOTE
SHUTDOWN
SWITCH
Figure 4-10. Remove Jumper
See
4-11. Connect the wiring to the external shut-
Figure
down switch (field supplied) to battery STOP terminals.
The STOP Terminals accept 20 to 12 AWG, solid or
stranded wire. As shown, 14 AWG THWN (600V) wiring
can be used and run in the same conduit as the REbus
wires.
WARNING:
+ STOP -
POWER SEARCH
TURN BATTERY
DISCONNECT "OFF"
AND DE-ENERGIZE
Figure 4-11. Connect To Remote Shutdown Switch
Installing PWRcell Battery
WARNING:
TURN BATTERY
REBUS BEFORE
TOUCHING
TERMINALS
REBUS BEFORE
TOUCHING
TERMINALS
012362
012363
19