Ethernet Communication Module IFD9506

7 Ethernet/IP Communication

7.1 Versions Supported

7.2 Functions Supported

Only the serial master mode is supported and Ethernet/IP master (Scanner) can communicate with the serial
equipment through the Implicit Message or Explicit Message.
(1) Implicit Message
The Ethernet/ IP master can conduct data exchange with IFD9506 to read the contents of the device
monitoring tables of IFD9506 (only the read action is allowed).
EIP Scanner
Data storage area in IFD9506
(2) Explicit Message
The Ethernet/ IP master can transmit the Modbus instruction to IFD9506 by placing it in an explicit message.
Reading multiple devices and writing to a single device are supported.
IFD9506 forwards the Modbus instruction to the serial slave and sends the response from the serial slave
back to the Ethernet/ IP master.
EIP Scanner
36
Module/ software
IFD9506
DCISoft
EIP Builder
IFD9506 (EIP Adapter/Modbus Master)
OUTPUT [0 - 127]
INPUT [0 - 127]
INPUT [128 - 227]
INPUT [228 - 234]
IFD9506 (EIP Server/Modbus Master)
Ethernet/IP parameters setting
Service Code
Class Code
Instance
Attribute
Version Number
V2.04 and above
V1.21 and above
V1.07 and above
Explanation
System-reserved area
The area where the contents of Word
device monitoring table are stored
The area where the contents of Bit
device monitoring table are stored
Slave
0x32
0x64
0x01
0x03
Modbus Slave
Modbus
DVP-PLC Operation Manual