Application Examples; Application Of Modbus Slave - Delta Electronics IFD9506 Operation Manual

Ethernet communication module rs485 ethernet
Hide thumbs Also See for IFD9506:
Table of Contents

Advertisement

10 Application Examples

10.1 Application of Modbus Slave

HMI controls the remote Ethernet device through IFD9506.
Application
(1) HMI sends out the instruction.
(2) Set the IP of slave IFD9506 to "192.168.1.6", station address to "7" and communication
(3) In the IFD9506 serial slave mode table, set the station addresses of the two devices to
(4) Set the IP of IFD9506 in master mode to "192.168.1.5", station address to "8" and
Steps
(5) HMI master and IFD9506 slave transmit data through RS-485.
(6) IFD9506 slave and IFD9506 master transmit data through Ethernet.
(7) The RS-485 terminal on IFD9506 master is connected to two devices, which are PLC
1.
The wiring:
2.
Setting IFD9506 slave
Step 1: Open "Basic" page, and select "Serial slave" in "Master configuration".
Step 2: Enter the device addresses and the relay IP addresses on "Serial Slave Mode" page.
DVP-PLC Operation Manual
format to "38400, 8, E, 1, RTU".
"1" and "3", both of their relay IP addresses to "192.168.1.5".
communication format to "38400, 8, E, 1, RTU".
at station address 0x0001 and PLC at station address 0x0003. Assume the
communication format is "38400, 8, E, 1, RTU".
Ethernet Communication Module IFD9506
53

Advertisement

Table of Contents
loading

Table of Contents