Ethernet Communication Module IFD9506

9.5.3 Serial Cache: Word Monitor

In the serial data word monitor, you must press "Apply" and save the settings on the Save page after setting the
station address of the serial slave, Modbus address and data length is over. After saving setting values, review
and enter the page to click "Start Monitor" for real-time monitoring.
The webpage only supports adding new items to be monitored and does not support the removal of items. To
remove existing items, please open DCISoft for removal action. When you enter the communication addresses in
Modbus (Hex) column, the function code 0x03 (word) is used to read data by default. If you want to use 0x04
function code to read data, please modify the settings in the Modbus (Dec) column as the values starting with 3
(e.g. 300001).

9.5.4 Serial IP Table

You must set the page when IFD9506 works in serial slave mode. IFD9506 receives the requests received from
the serial port and then sends them to the IP address specified in the table according to the Modbus station
address in the instruction. After setting is over, press "Apply" and save the settings on the Save page.