flowair T-box User Manual
Hide thumbs Also See for T-box:

Advertisement

Quick Links

instrukcja obsługi / user manual / руководство пользователя / Gebruikershandleiding

Advertisement

Table of Contents
loading

Summary of Contents for flowair T-box

  • Page 1 instrukcja obsługi / user manual / руководство пользователя / Gebruikershandleiding...
  • Page 2: Table Of Contents

    Do not place it near heat sources, lighting, air First run ......................68 inlets, windows and door openings, etc. Main screen ....................If temperature sensor was chosen in a T-Box menu as Main menu ..................... „installed in unit”, T-box controller can be mounted out Time ......................
  • Page 3: Technical Data

    * Applies to all devices connected to T-box controller in line ** In case of Cube devices addressing is beeing done by service during first startup In the case, when T-box in BMS network is the last device, SW1 Last DRV...
  • Page 4: First Run

    FIRST RUN Language Data August Selection of language Setting of date active language Time Devices 13PM Setting of time Searching of connected units. www.flowair.com...
  • Page 5 • if address have been set correctly; each device must have a different address set, (in Cube devices the address is set by the service during the first start-up) • if the SW2 dipswitch on the last device in line is set to T120 position. (in Cube devices, the dipswitch is set by the service during the first start-up) www.flowair.com...
  • Page 6: Main Screen

    BMS mode active integrated units version calendar active restore factory settings BMS settings calendar active - settings forced the icon informs about changed position of OXeN dampers, or about Cube device start- up, the fans are suspended during this time. www.flowair.com...
  • Page 7: Time

    2 s the August calendar icon on main screen). Ad hoc settings stays as long as time of current event in calendar. With start of next event, units will operate according to programmed settings. Setting of date www.flowair.com...
  • Page 8: Calendar

    KM – additional settings for KM group copying events on the following days OXeN – additional settings for OXeN group Cube – additional setting of Cube group. removing the events moving to the next day event – system ON 7:00AM event – system OFF 9:00AM www.flowair.com...
  • Page 9 For OXeN it is possible to set an air flow in current event. opening degree in current event. When the dampers are closed (no ventilation), it is possible to select the operating mode of the fan after reaching desired temperature. Fan can operate continuously or be turned off. www.flowair.com...
  • Page 10 Cube will work in thermostatic mode - they will turn off after reaching the preset Therm temperature in the room. When Auto mode is activated, the Cube’s throttle will be adjusted automatically until the set temperature is economically reached. Auto www.flowair.com...
  • Page 11: Language

    PN day Language day with already programmed operation schedule – you can also copy here the events from PN day Language day without programmed operation schedule active language www.flowair.com...
  • Page 12: Integrated Units

    Integrated units Reset Devices Reset to default settings? Restore default settings. searching for units integrated with system active deactivated unit unit – not operating System information LEO M 01 CURTAIN MAIN DRV-V 2.1 2.0.0-2d-..long press displays the DRV software www.flowair.com...
  • Page 13: Antifreeze

    LEO and KM units are turned on: leading sensor is the sensor built • valves (if installed) opens, in T-box controller • fan is turned on at 100% of efficiency, leading sensor is the local sensor. When it is •...
  • Page 14: Controller Lock

    DRV KM control module or a controller in the Cube controller will be locked automatically. device. In the menu, indicate to which device the central unit is connected. In the example given, the control unit has been connect- ed to DRV KM No. 7. www.flowair.com...
  • Page 15: Information Menu

    System information BMS – settings System information Basic information about software and hardware version. ID – setting unit adress: from 1 to 247 BAUD – setting data transmission speed: from 9600 to 230400 bit/s Physical layer: Modbus RTU Protocol: RS485 www.flowair.com...
  • Page 16: Leo Fan Heaters

    – valve is constantly closed, fan operates continuously at selected speed Auto – automatic fan regulation depending on desired and measured temperature Manual – fan operates with constant, selected speed www.flowair.com...
  • Page 17 1, 2, 3 or be turned off - select OFF. Airflow AUTO In AUTO mode after reaching desired temperature fan can operate continously on selected step: 1, 2, 3 or be turned off - select OFF. www.flowair.com...
  • Page 18 The heater must be equipped with T3 sensor (optional equipment). activation of destratification mode setting of temperature difference (difference between temperature under the ceiling and temperature in the occupied zone), at which LEO heaters will be turned on selection of heaters, which should operate in destratification mode www.flowair.com...
  • Page 19 Readings Readings ON/OFF Temperature Temperature in valve under the the room ceiling To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 20: Leo Cool Fan Cooler/Heater

    – heating medium valve is opened when measured temperature is higher than desired temperature ventilation – valve is constantly closed, fan operates continuously at selected speed Auto – automatic fan regulation depending on desired and measured temperature Manual – fan operates with constant, selected speed www.flowair.com...
  • Page 21 LEO COOL selected step: 1, 2, 3 or be turned off - select OFF. Airflow AUTO In AUTO mode after reaching desired temperature fan can operate continously on selected step: 1, 2, 3 or be turned off - select OFF. www.flowair.com...
  • Page 22 Readings LEO COOL Readings ON/OFF Temperature in valve the room To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 23 www.flowair.com...
  • Page 24: Leo El Fan Heaters

    – heaters are OFF, fan operates readings at selected speed continuously www.flowair.com...
  • Page 25 - 3 steps In MANUAL mode after reaching desired heating power setting - 2 steps temperature fan can operate continously on selected step: 1, 2, 3 or be turned off - select OFF. www.flowair.com...
  • Page 26 The heater must be equipped with T3 sensor (optiona- lequipment). activation of destratification mode setting of temperature difference (difference between temperature under the ceiling and temperature in the occupied zone), at which LEO heaters will be turned on selection of heaters, which should operate in destratification mode www.flowair.com...
  • Page 27 Readings LEO EL Readings Temperature under the ceiling Temperature in the room Chosen heat power To read temperatures near the unit, external temperature sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 28: Km Mixing Chambers

    – valve is opened when measured temperature is higher than desired temperature readings filters operating status ventilation – valve is constantly closed, fan operates continuously at selected step selection of leading sensor roof fan setting dampers setting according to external temperature www.flowair.com...
  • Page 29 • 2 – second step of alarm from gas detector When the dampers are closed (no ventilation), it is possible to select the operating mode of the fan after reaching desired temperature. Fan can operate continuously or be turned off. www.flowair.com...
  • Page 30 When the dampers are closed (no ventilation), it is possible to select the operating mode of the fan • 2 – second step of alarm from gas detector after reaching desired temperature. Fan can operate continuously or be turned off. www.flowair.com...
  • Page 31 Temperature in the room ON – automatic setting of dampers according to external temperature is active – see p. 37 Temperature of air supplied into the room dampers opening degree ON/OFF valve Temperature of heating medium on return pipe www.flowair.com...
  • Page 32 Value must be reset. Alarm does not affect the operation of the unit. Leading sensor is the ambient air temperature sensor (built in T-box or local, near the unit). Filters operating time limit When temperature in the room is not reached, SRX3d valve is open in 100%.
  • Page 33 Positive value means that the roof fan removes more air than the KM supplies (under-pressure). Setting „+100%” means continuous operation of the roof fan. Negative value means that the roof fan removes less air than the KM supplies (overpressure). Setting „-100%” means operation of the KM only. www.flowair.com...
  • Page 34: Leo D Destratificators

    When amount of heat is insufficient, LEO heaters are turned on automatically. Manual – destratificator operates in ON/OFF mode. It is turned on when temperature under the ceiling is higher than set temperature. www.flowair.com...
  • Page 35 To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control Settings of manual operating mode module. MANUAL settings Destratificator operates in ON/OFF mode. It is turned on when temperature under the ceiling is higher than set temperature. www.flowair.com...
  • Page 36: Robur Gas Heaters

    – automatic selection of the burner readings power depending on the measured temperature heating-manual – manual selection of the burner thermal protection settings power ventilation mode - fan is working continuously, burner is OFF unit is OFF www.flowair.com...
  • Page 37 - ON or be temperature ready for restart turned off - OFF Readings ROBUR Readings outlet air temp., STB protection. temperature in the room www.flowair.com...
  • Page 38: Robur Mixing Chambers

    – manual selection of the burner power readings ventilation mode – fan is working thermal protection settings continuously, burner is OFF unit is OFF filters operating status roof fan setting www.flowair.com...
  • Page 39 Readings damper setting in heating-continues mode ROBUR KM Readings outlet air temp., STB protection. external temperature temperature in the room dampers opening degree ON – automatic setting of dampers according to external temperature is active. www.flowair.com...
  • Page 40 Value must be reset. Alarm does not affect the operation of the unit. temperature ready for restart Filters operating time limit ROBUR KM Filters Value should be set according to building contamination level. www.flowair.com...
  • Page 41 ROBUR KM supplies (under-pressure). Setting „+100%” means continuous operation of the roof fan. Negative value means that the roof fan removes less air than the ROBUR KM supplies (overpressure). Setting „-100%” means operation of the ROBUR KM only. www.flowair.com...
  • Page 42: Elis Air Curtains

    Door sensor has a priority. Without it’s signal unit will not run antifreeze heating – valve is opened when measured temperature is lower than desired temperature ventilation – valve is constantly closed, fan operates continuously at selected step www.flowair.com...
  • Page 43 ∞ value, then valve is constantly open. specified period of time or be turned off - select Valve delay time must be shorter than fan delay OFF. time. www.flowair.com...
  • Page 44: Elis Duo Air Curtain-Fan Heater Combo Units

    – 3-steps Readings selection of operating mode setting of delay times Readings readings antifreeze To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 45 – valve is opened when measured temperature is lower than desired temperature ventilation – valve is constantly closed, fan operates continuously at selected step Fan heater operates always according to temperature set on the controller, regardless K1/K2 mode. www.flowair.com...
  • Page 46 0:00 - 10:00 minutes, every 0:30 s. Value ∞ - valve heater can operate continously on selected step: 1, is constantly open. 2, 3 or be turned off - select OFF. www.flowair.com...
  • Page 47 Temperature in the room ON/OFF valve fans stops and valve is open to 100%. The unit must be equipped with T3 sensor (optional equipment). To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 48: Slim Air Curtains

    Door sensor has a priority. Without it’s signal unit will not run antifreeze heating – valve is opened when measured temperature is lower than desired temperature ventilation – valve is constantly closed, fan operates continuously at selected step www.flowair.com...
  • Page 49 ∞ value, then valve is constantly open. specified period of time or be turned off - select Valve delay time must be shorter than fan delay OFF. time. www.flowair.com...
  • Page 50 PT-1000 must be connected to DRV control perature in the room drops below desired temperature fans stops and valve is open to 100%. The unit must be module. equipped with T3 sensor (optional equipment). Temperature in ON/OFF valve the room www.flowair.com...
  • Page 51 www.flowair.com...
  • Page 52: Oxen Heat Recovery Units

    Operation without heat recovery – supply air is directed via by-pass without heat recovery („freecooling”/„free-heating”). selection of leading sensor Automatic change of operating mode with or this icon inform that dampers are during without heat recovery, depending on temperature change of position, fan are stopped www.flowair.com...
  • Page 53 Change will only be active in given calendar event. Three values of air flow should be defined: • normal operation status • 1 – first step of alarm from gas detector • 2 – second step of alarm from gas detector www.flowair.com...
  • Page 54 Desired temperature of supply air External temperature Temperature in the room Temperature of removed air Temperature of air supplied into the room ON – status of by-pass dampers Temperature of heating medium ON – status of external dampers on return pipe ON/OFF valve www.flowair.com...
  • Page 55 Filters active temperature sensor Control of the filters pollution Leading sensor is the ambient air temperature sensor (built in T-box or local, near the unit). OXeN When temperature in the room is not reached, Filters SRX3d valve is open in 100%. When temperature...
  • Page 56: Oxen El Heat Recovery Units

    AUTO this icon inform also that fans cooling the heater manual setting of heating power MANUAL www.flowair.com...
  • Page 57 OXeN EL OXeN EL Readings Readings External temperature Temperature of removed air ON – status of by-pass damper Temperature in the room ON – status of external dampers Temperature of air supplied into the room chosed of heating power www.flowair.com...
  • Page 58 3 – 8,5 kW Control of the filters pollution 2 – 5,5 kW 1 – 3,5 kW OXeN EL Filters Set the required alarm value, where 1 means an alarm a small filter pollution, 5 means an alarm a very pollution filter. www.flowair.com...
  • Page 59: Cube Rooftop Units

    Auto setpoint for cooling or heating depending on the active operating mode of the Cube. For cooling, optimal airflow is horizontal and for heating it is vertical manual mode - fixed swirl diffuser setting Manual Manual www.flowair.com...
  • Page 60 The selection of the leading/master sensor from: supply air, exhaust air and wall temperature sensors is made during first startup. It is also possible to define built in sensor in T-box sensor he leading sensor www.flowair.com...
  • Page 61 The change will only be active in that calendar zone Manual setting of the recirculation damper position Manual The position of the recirculation damper is changed automatically Auto depending on air temperatures. www.flowair.com...
  • Page 62 Vent - ventilation Heat - heating HeatRec - heat recovery Room temperature reading from the T-box controller’s Cool - cooling built-in sensor or from the optional NTC wall-mounted CoolRec - cool recovery sensor, connected to the Cube control box/enclosure...
  • Page 63 Forcing - active signal from an external detector (option) Thermostat - the device works in thermostatic mode NightCool - the device works in the night cooling mode (applies to Climatix regulation) Overrun - cooling down process Defrosting - defrosting the heat pump (optional) www.flowair.com...
  • Page 64: Alarms

    • Antifreeze heat recover exchanger ON • Roof fan fuse no communication between DRV and antifreeze mode of heat recovery check the fuse of the roof fan on the T-box, check connection and DRV exchanger is on DRV board power supply • Filter work time •...
  • Page 65 +48 58 669 82 20, fax: +48 58 627 57 21 e-mail: info@flowair.pl www.flowair.com Declaration Of Conformity UE FLOWAIR hereby declare that the T-box controller were produced in accordance to the following Europeans Directives: 2014/30/UE – Electromagnetic Compatibility (EMC) 2014/35/UE –...