Viessmann VITOCROSSAL 200 Service Instructions Manual page 47

Gas condensing boiler with matrix cylinder burner
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Air pressure switch
Combustion chamber pressure monitoring function (LDW2)
B
To monitor the combustion chamber
pressure, the switching threshold of air
pressure switch 2 (LDW2) is monitored
in all operating phases (except during
safety and stabilising time).
Air pressure switch C triggers a fault
shutdown at the burner control unit under
the following circumstances:
■ If the combustion chamber pressure is
outside the permissible range in the
pre-purge phase, in control mode or in
the post-purge phase after 2 attempts.
The fault shutdown is shown with fault
indicator "F FB" on the burner control unit
display (see page 48) and can be reset
by pressing reset button B.
(cont.)
C
Rated
Rated
heating
heat in-
output
put
P
Q
max
max
(50/30 °C)
[net cv]
in kW
in kW
400
500
620
Air pressure switch
LDW2 set val-
ue
(H
)
i
in mbar (kPa)
381
474
5 (0.5)↑
593
47