Commissioning, inspection, maintenance
Further details regarding the individual steps
Checking the gas type
1. Check the gas type and Wobbe index
(Wo) with your gas supply utility.
■ With the natural gas E setting, the
boiler can be operated in the
Wobbe index range 12.0 to
3
16.1 kWh/m
■ With the LPG P setting, the boiler
can be operated in the Wobbe
index range 20.3 to 21.3 kWh/m
(72.9 to 76.8 MJ/m
Rated heating output
Restrictor for natural gas E
Restrictor for LPG P
3. Record the gas type in the report (on
page 86).
10
(43.2 to 58.0 MJ/m
3
).
kW
7 mm
7 mm
2. In the delivered condition, the burner
is set up for natural gas E. If required,
convert the burner to a different gas
type (see from page 11) in accord-
ance with details provided by your
gas supply utility.
3
).
Note
The 500 kW burner requires a natural
3
gas restrictor. A natural gas restrictor
is not required for the 400 and
620 kW burners.
400
−
14.0
(cont.)
500
21.5
14.8
620
−
17.2