1

Installing the switch

IMPORTANT:
Keep the packages of the switch and the components for future use.

Confirming installation preparations

Before you install the switch, verify that:
You have read "Preparing for installation" carefully and the installation site meets all the
requirements.
A 19-inch rack is ready for use and the rack has enough space to accommodate the switch.
For information about how to install a rack, see the rack installation guide.
The rack is sturdy and reliably grounded.
No debris exists inside or around the rack.
The rack can provide power as required by the switch. For information about the system power
consumption, see "Module power consumption and system power consumption." For power
supply specifications such as power input mode and rated input voltage, see "Power supplies."
The total height of the switches to be installed is not higher than the available installation height
of the rack and enough clearance is reserved for cable routing.
The switch is ready for installation and has been carried to a place near the rack and convenient
for moving.

Installing the switch in a rack

Switch dimensions and rack requirements

To mount the switch in an enclosed rack, make sure the rack meets the requirements described in
Table1-1.
Table1-1 Rack requirements
Switch dimensions
Height—133 mm (5.24 in) (3 RU).
Width—440 mm (17.32 in).
Chassis depth—895 mm (35.24 in)
Total depth—1013 mm (39.88 in)
104 mm (4.09 in) from the rack-facing
surface of the mounting brackets to the
front ends of the cable management
brackets
909 mm (35.79 in) from the rack-facing
surface of the mounting brackets to the
power supply handles at the chassis rear
NOTE:
As a best practice, use a rack that has a single door at the front.
Rack requirements
A minimum of 1.1 m (3.61 ft) in depth
(recommended)
A minimum of 130 mm (5.12 in) from the front
rack post to the front door
A minimum of 950 mm (37.40 in) from the front
rack post to the rear door
1-1