Fujitsu ADUH09LUAS1 Service Manual page 58

Hide thumbs Also See for ADUH09LUAS1:
Table of Contents

Advertisement

Check point 4. Check serial signal (Forward transfer signal)
Check serial signal (Forward transfer signal)
Check if indicated value swings between AC 30 V and AC 130 V at outdoor unit terminal 2—3.
If it is abnormal, replace main PCB.
Check point 1-2. Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
BLACK
1
WHITE
2
3
RED
BLACK
L
WHITE
N
End
End
+
-
- (03-6) -
2. Troubleshooting with error code