Fujitsu ADUH09LUAS1 Service Manual page 126

Hide thumbs Also See for ADUH09LUAS1:
Table of Contents

Advertisement

 Model: AOUH12LUAS1
Fan speed is defined by outdoor temperature and compressor frequency.
• Outside air temperature zone selection
Cooling
Fan step
Y zone
S-HIGH2
S-HIGH1
1,050
HIGH
1,050
10
9
1,050
8
7
6
5
4
3
2
1
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,100 rpm
3-2. Outdoor fan control
Outside air
temperature rises
69.8°F
( 21°C)
53.6°F
( 12°C)
35.6°F
( 2°C)
17.6°F
( -8°C)
Heating
Y zone
1,100
1,100
1,100
1,100
1,100
810
870
810
760
560
760
560
680
440
530
440
500
440
420
440
420
Outside air
temperature drops
Y zone
Z zone
F zone
G zone
H zone
Dry
Cooling or dry at low outdoor temp.
Z zone
1,050
850
810
850
810
770
560
630
560
440
440
320
440
320
440
320
440
320
- (04-14) -
66.2
°F
(19°C)
50.0
°F
(10°C)
32.0
°F
(0°C)
14.0°F
( -10°C)
F zone
G zone
320
270
320
270
320
270
270
230
270
230
270
230
270
230
270
230
270
230
Unit: rpm
H zone
270
270
270
230
230
230
230
230
230
3. Fan control