Fujitsu ADUH09LUAS1 Service Manual page 140

Hide thumbs Also See for ADUH09LUAS1:
Table of Contents

Advertisement

Sensor ID
Cooling thermostat On/Off (External
00
158
output)
Requested cooling strength On/Off
00
159
(External output)
External heater On/Off (External
00
160
output)
Heating operation status (External
00
161
output)
External output command by remote
00
162
controller (External output)
01: Outdoor unit
01
000
Outdoor temp.
01
001
Discharge temp.
01
003
Heat exchanger middle temp.
01
004
Heat exchanger outlet temp.
01
007
Compressor temp.
01
050
Fan 1 rotation number
01
055
Compressor rotation number
Expansion valve (Upstream during
01
060
heating)
01
080
4-way valve output status
01
100
Operating current
01
110
Outdoor unit total power-on hours
Compressor total heating operation
01
111
hours
Compressor total cooling operation
01
112
hours
01
113
Compressor total operation hours
Outdoor unit fan 1 total operation
01
114
hours
6-11. Unit status monitoring and the detected value indication
Available Sensor ID
Item
01: °F or °C
01: °F or °C
01: °F or °C
01: °F or °C
01: °F or °C
07: Cooling/
- (04-28) -
Unit
0: Off, 1: On
NOTE: The value is output even if
00: —
the function setting or
rotary switch is not set.
0: Off, 1: On
NOTE: The value is output even if
00: —
the function setting or
rotary switch is not set.
0: Off, 1: On
NOTE: The value is output even if
00: —
the function setting or
rotary switch is not set.
0: Off, 1: On
NOTE: The value is output even if
00: —
the function setting or
rotary switch is not set.
0: Off, 1: On
NOTE: The value is output even if
00: —
the function setting or
rotary switch is not set.
03: rpm
04: rps
05: pls
0: Cooling, 1: Heating
Heating
09: A
11: h
11: h
11: h
11: h
11: h
Remarks
6. Various control