E: 51. Indoor Unit Fan Motor Error (Indoor Unit) - Fujitsu ADUH09LUAS1 Service Manual

Hide thumbs Also See for ADUH09LUAS1:
Table of Contents

Advertisement

2-14. E: 51. Indoor unit fan motor error (Indoor unit)

→ired remote
Indicator
controller
Detective actuator
Indoor unit
Forecast of cause
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
If fan or bearing is abnormal, replace it.
Check point 2. Check ambient temperature around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat)
Upon the temperature coming down, restart operation.
Check point 3. Check indoor unit fan motor
Check Indoor unit fan motor. (Refer to indoor unit fan motor in
03-43.)
If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
Check point 4. Replace main PCB
If Check Point 1 to 3 do not improve the symptom, replace main PCB.
2-14. E: 51. Indoor unit fan motor error (Indoor unit)
Error code
main PCB
Fan motor
End
→hen the condition that actual frequency of indoor fan is
below 1/3 of target frequency is continued more than 56
seconds.
Fan rotation failure
Fan motor winding open
Motor protection by surrounding temperature rise
Control PCB failure
Indoor unit fan motor failure
"Service parts information"
- (03-18) -
E: 51
on page
2. Troubleshooting with error code

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents