External Input And Output; External Input - Fujitsu ACUH09LUAS1 Design & Technical Manual

Cassette type
Hide thumbs Also See for ACUH09LUAS1:
Table of Contents

Advertisement

8. External input and output

CN65
PCB

External input

Operation/Stop
Forced stop
Indoor unit
Operation/Stop
Forced
thermostat off
External input
and output
(UTY-XCSX)
8-1. External input
• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
• The wire connection should be separate from the power cable line.
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
8-1. External input
Indoor unit PCB
Terminal
(Ext. in)
External output Connector
Operation status
Error status
Indoor unit fan
operation status
External heater
output
Operation status
Error status
Indoor unit fan
operation status
External heater
output
Rotary switch
SW2
SW1
CN47
(Ext. out)
Input select
Terminal
Dry contact
CN47
CN47
Input 1/
Input 2
Dry contact/
Apply voltage
Input 1
Output 1
Output 2
Output 3
- 24 -
External input and output PCB
External
Input
connect kit
signal
(Optional
parts)
Edge
UTY-XWZXZG
Edge/
Pulse
Edge
Terminal
1
2
8. External input and output