• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer's anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
A
Cooling
3
CFM (m
/h)
Heating
W
Cooling
dB (A)
Heating
Dimensions
in (mm)
(H × W × D)
Fin pitch
FPI
Rows × Stages
Pipe type
Type (Material)
Fin type
Surface treatment
W
Type
lb oz
Charge
g
Type
3
3
Amount
in
(cm
)
Material
Color
in (mm)
lb (kg)
Liquid
in (mm)
Gas
ft (m)
Cooling
°F (°C)
Heating
Material
Tip diameter
in (mm)
- 72 -
Inverter heat pump
AOUH09LUAS1
AOUH12LUAS1
208/230 V ~ 60 Hz
Outdoor unit
187—253 V
4.6
1,171 (1,990)
906 (1,540)
1,089 (1,850)
Propeller fan × 1
23
44
48
Main1: 19-13/16 × 34-11/16 ×
11/16
(504 × 881 × 18.19)
Main2: 19-13/16 × 33-1/2 ×
11/16
(504 × 851 × 18.19)
Main1: 1 × 24
Main2: 1 × 24
Aluminum
DC rotary × 1
900
2lbs.3oz.
2lbs.10oz.
1,000
20.7 (340)
Steel sheet
Approximate color of Munsell 10YR 7.5/1.0
21-5/16 × 31-7/16 × 11-7/16
(542 × 799 × 290)
23-11/16 × 37 × 14-3/4
(602 × 940 × 375)
70 (32)
77 (35)
Ø 1/4 (Ø 6.35)
Ø 3/8 (Ø 9.52)
49 (15)
66 (20)
14 to 115 (-10 to 46)
-5 to 75 (-21 to 24)
Ø 1/2 (Ø 13.0) (I. D.), Ø 5/8 to 11/16 (Ø 16.0 to 16.8) (O. D.)