ABB Relion 670 Series Commissioning Manual page 153

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UUS Rev. K
If the neutral VT is not available, then the setting NeutVoltMeas is set to Not available.
1.
Set the following parameters:
2.
Activate RESETCOMP input to ensure that the stored values are reset.
3.
The expected output is monitored in the following path from the local HMI client: Main menu /Test/
Function status /Unbalance protection/CapBankPhaseVoltageDiff(87V, Ud>)/SCPDPTOV(87V,
Ud>):x/Outputs , where x = instance number.
4.
check the respective operation of warning, alarm, and trip.
Step no.
4-a*
4-b
4-c
4-d
4-e **
4-f
4-g
Table continues on next page
Bay control REC670
Commissioning manual
Operation = Enable
tDefWrn =5 s; tDefAlm =5 s; tDefTrip =5 s
SCBGndType =Ungrounded
NeutVoltMeas =Not available
Udif> =10% UB
UdifAlm> =8% UB
UdifWrn> =5% UB
UMin> =50% UB
VoltRatioL1 =0.5
Changes after step 2
Inject constant bus voltages of U
U
= 60 V at 240°, and U
L2
secondary at rated frequency
Inject constant tap voltage of U
secondary at rated frequency
Activate binary input RESETCOMP for 1 s
Inject U
= 28.17 V in secondary at rated
TapL1
frequency
Activate binary input TRIGCOMP for 1 s
Inject U
= 29.50 V in secondary at rated
TapL1
frequency
Inject U
= 30.20 V in secondary at rated
TapL1
frequency
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Expected output
= 60 V at 0°,
L1
= 60 V at 100° in
L3
= 30 V in
UTAPL1 should show 109.09 kV
TapL1
RESETCOMP Test
USEDURATL1 should show 0.5 (VoltRatioL1)
TRIGCOMP Test
Repeat
Sub-step 4–a
WARNING Signal Test
ALARM Signal Test
Repeat
Sub-step 4–a
and
Sub-step 4–b
Testing functionality by secondary injection
UL1, UL2, and UL3 should show 218.18
kV
UNSCB should show 6.94kV
DIFURATL1 should become HIGH
URATIOL1 and USEDURATL1 should
show 0.4 and 0.5 respectively
The output COMPEXED should become
HIGH for 100 ms and LASTCOMP output
should display the date and time of
compensation
URATIOL1 and USEDURATL1 should
show 0.4
DIFURATL1 should become LOW
WARNING and WRNL1 signals should
become HIGH after a time delay given by
the setting tDefWrn
PUDIFL1 should show 5.28 %
ALARM and ALML1 signals should
become HIGH after a time delay given by
the setting tDefAlm
PUDIFL1 should show 8.06%
Section 11
147