PNOZ X9
Faults – Interference
Earth fault: The supply voltage fails and the safety contacts open. Once the cause of
}
the respective fault has been rectified and the supply voltage is switched off for approx.
1 minute, the unit is ready for operation again.
Contact malfunctions: If the contacts have welded, reactivation will not be possible after
}
the input circuit has opened.
LED "POWER" does not light: Short circuit or no supply voltage.
}
Dimensions in mm
Operating Manual PNOZ X9
19526-EN-09
75 (2.95")
87 (3.42")
90 (3.54")
15