Page 2
• Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
CONTENTS Part 1. INDOOR UNIT................1 1. Model lineup ....................2 1-1. Indoor unit connection patterns..................3 2. Specifications....................9 2-1. Compact cassette type ....................9 2-2. Mini duct type.........................11 2-3. Slim duct type ........................13 2-4. Medium static pressure duct type ..................15 2-5. Wall mounted type ......................16 2-6.
Page 4
CONTENTS (continued) 7-4. Medium static pressure duct type ................114 7-5. Wall mounted type .......................115 7-6. Ceiling type ........................118 7-7. Floor type........................119 8. Noise level curve..................120 8-1. Compact cassette type ....................120 8-2. Mini duct type.......................123 8-3. Slim duct type ......................126 8-4. Medium static pressure duct type ................129 8-5.
Page 5
CONTENTS (continued) 14-8.Wired remote controller (UTY-RLRG) .................274 14-9.Wired remote controller (UTY-RNRGZ*) ..............274 14-10.Simple remote controller (UTY-RSNGM) ..............275 15. Accessories ....................276 15-1.Compact cassette type ....................276 15-2.Mini duct type......................277 15-3.Slim duct type ......................279 15-4.Medium static pressure duct type ................280 15-5.Wall mounted type ......................281 15-6.Ceiling type .........................284 15-7.Floor type ........................285 16.
1-1. Indoor unit connection patterns ¢ 4-unit multi-split type AOHG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — — — — — — — — — —...
Page 12
AOHG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — Numbers in column Unit 1 to 4, and Total indicate the indoor unit capacities as follows: 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..- 4 - 1-1.
Page 13
¢ 5-unit multi-split type AOHG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — —...
Page 14
AOHG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
Page 15
AOHG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
Page 16
AOHG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total Numbers in column Unit 1 to 5 and Total indicate the indoor unit capacities as follows: 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..*: As for the 22 model, wall-mounted type indoor unit is only connectable.
2. Specifications 2-1. Compact cassette type Model name AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.19 0.22 HIGH Cooling QUIET Airflow rate HIGH...
Page 18
Model name AUXG18KVLA AUXG22KVLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.30 0.62 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Turbo fan × 1 Motor output HIGH Cooling...
2-2. Mini duct type Model name ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.29 0.33 0.38 0.58 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET...
Page 20
Model name ARXG18KSLAP Power supply 1Ø 230 V ~ 50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.49 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 3 Motor output Recommended static pressure 0 to 50...
2-3. Slim duct type Model name ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.33 0.30 0.35 0.51 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
Page 22
Model name ARXG18KLLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.44 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 3 Motor output Recommended static pressure 0 to 90 HIGH...
2-4. Medium static pressure duct type Model name ARXG22KMLB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.60 HIGH 1,100 Cooling QUIET Airflow rate HIGH 1,100 Heating QUIET Type × Q'ty Sirocco fan ×...
2-5. Wall mounted type Model name ASHG07KGTB ASHG09KGTB ASHG12KGTB ASHG14KGTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
Page 25
Model name ASHG18KMTB ASHG22KMTB ASHG24KMTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power 37.5 47.0 61.6 Running current 0.35 0.39 0.44 HIGH 1,060 1,170 Cooling QUIET Airflow rate HIGH 1,020 1,060 1,170 Heating QUIET...
Page 26
Model name ASHG07KMCC ASHG09KMCC ASHG12KMCC ASHG14KMCC Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Crossflow fan ×...
Page 27
ASHG07KETA ASHG09KETA ASHG12KETA ASHG14KETA Model name ASHG07KETA-B ASHG09KETA-B ASHG12KETA-B ASHG14KETA-B Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
2-6. Ceiling type Model name ABHG18KRTA ABHG22KRTA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.21 0.25 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco × 2 Motor output HIGH Cooling...
2-7. Floor type Model name AGHG09KVCA AGHG12KVCA AGHG14KVCA Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.18 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Cross flow fan ×...
3. Dimensions 3-1. Compact cassette type ¢ Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA Unit: mm Grid type grille Hanging bolt position IR receiver Drain hose View A Ceiling Control Box View C View B a: Ceiling openings Cassette grille (Option [Grid type])
Page 31
Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) 07 and 09 models 12 or larger models Standard 2,700 High ceiling —...
3-2. Mini duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, and ARXG14KSLAP Unit: mm Rear view View A Drain port P 100 × 6 = 600 Top view Side view Front view Bottom view - 24 - 3-2. Mini duct type 3.
Page 33
¢ Model: ARXG18KSLAP Unit: mm Rear view View A Drain port P 100 × 8 = 800 Top view Side view Front view Bottom view - 25 - 3-2. Mini duct type 3. Dimensions...
Page 34
Installation space requirement Provide sufficient installation space for product safety. Unit: mm Strong and durable ceiling Indoor unit Left Right side side or more* or more *: 400 or more when drain from drain pipe • When intaking air from back: •...
3-3. Slim duct type ¢ Models: ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, and ARXG14KLLAP Unit: mm View A Rear view Drain port 100 x 6 = 600 Side view Top view Front view Bottom view - 27 - 3-3. Slim duct type 3. Dimensions...
Page 36
¢ Model: ARXG18KLLAP Unit: mm Rear view View A Drain port 100 × 8 = 800 Top view Side view Front view Bottom view - 28 - 3-3. Slim duct type 3. Dimensions...
Page 37
Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: mm 300 or more Strong and durable ceiling 20 or more Indoor unit Left Right side side 20 or more Service access Ceiling or more or more Floor ...
3-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Unit: mm Φ205 Φ3.2 Front view 1,177 Gas pipe Drain port Liquid pipe Φ200 Knockout Drain port for fresh air Φ5 Φ3.2 80 80 P125 × 3 = 375 P125 × 3 = 375 Φ5 1,015 1,135...
Page 39
Maintenance space requirement Unit: mm • Provide a service access for maintenance purposes. Maintenance hole Control box • The service access necessary for fan units and filter maintenance. Maintenance hole Intake panel Control box 1,550 • When using a square duct P174 ×...
3-5. Wall mounted type ¢ Models: ASHG07KGTB, ASHG09KGTB, ASHG12KGTB, and ASHG14KGTB Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 32 - 3-5. Wall mounted type 3. Dimensions...
Page 41
Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors.
Page 42
¢ Models: ASHG18KMTB, ASHG22KMTB, and ASHG24KMTB Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 34 - 3-5. Wall mounted type 3. Dimensions...
Page 43
Installation space requirement Provide sufficient installation space for product safety. Unit: mm Wall hook bracket 70 or more 40 or more Outline of the indoor unit 160 or more 117 or more 1,500 or more The flare connection part should be installed outdoors.
Page 44
¢ Models: ASHG07KMCC, ASHG09KMCC, ASHG12KMCC, and ASHG14KMCC Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 36 - 3-5. Wall mounted type 3. Dimensions...
Page 45
Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors.
Page 46
¢ Models: ASHG07KETA, ASHG09KETA, ASHG12KETA, ASHG14KETA, ASHG07KETA-B, ASHG09KETA-B, ASHG12KETA-B, and ASHG14KETA-B Unit: mm (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 38 - 3-5. Wall mounted type 3. Dimensions...
Page 47
Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 40 or more Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors.
3-6. Ceiling type ¢ Models: ABHG18KRTA and ABHG22KRTA Unit: mm 1,080 49 84 125 103 Side view Top view ø100-mm hole Rear view Suspension bolt pitch Dimensions Indoor unit (Top view) (Space required for installation) The length of the bolt here is 30 mm.
Page 49
¢ Installation space requirement Unit: mm Ceiling Indoor unit 30 or more Ceiling 200 or more 0 or more Obstruction Floor Required ceiling height varies according to the ceiling mode setting of function setting No. 20. Ceiling height (m) Ceiling mode Standard High ceiling 18, 22 models...
3-7. Floor type ¢ Models: AGHG09KVCA, AGHG12KVCA, and AGHG14KVCA Unit: mm Side view Front view Installation space 100 or more 80 or more 80 or more 50 or more 150 or below from the floor - 42 - 3-7. Floor type 3.
Page 51
WARNING • The appliance shall be installed, operated and stored in a room with a floor area larger than X Minimum room area Amount of refrigerant charge M (kg) X (m M ≤ 1.22 1.22 < M ≤ 1.23 12.99 1.23 <...
4-2. Mini duct type and Slim duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, ARXG14KSLAP, ARXG18KSLAP, ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP, and ARXG18KLLAP WLAN adapter, Converter etc. (Option) - 45 - 4-2. Mini duct type and Slim duct type 4. Wiring diagrams...
5. Air velocity and temperature distributions 5-1. Compact cassette type ¢ Models: AUXG07KVLA and AUXG09KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Vertical airflow direction louver: up 0.25 0.25...
Page 62
• Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions...
Page 63
¢ Model: AUXG12KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 4 (m) Unit : m/s Side view Vertical airflow direction louver: up 0.25 0.25 4 (m)
Page 64
• Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data...
Page 65
¢ Model: AUXG14KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 0.25 4 (m) Unit : m/s Side view Vertical airflow direction louver: up 0.25 0.25 4 (m)
Page 66
• Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data...
Page 67
¢ Model: AUXG18KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25 0.25...
Page 68
¢ Model: AUXG22KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25...
5-2. Mini duct type ¢ Model: ARXG07KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 70
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 71
¢ Model: ARXG09KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 72
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 73
¢ Model: ARXG12KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 74
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 75
¢ Model: ARXG14KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 76
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 77
¢ Model: ARXG18KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 78
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
5-3. Slim duct type ¢ Model: ARXG07KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 80
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 81
¢ Model: ARXG09KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 82
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 83
¢ Model: ARXG12KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 84
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 85
¢ Model: ARXG14KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 86
• Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
Page 87
¢ Model: ARXG18KLLAP NOTE: This data is measured installing the Auto louver grille kit (option). Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
Page 88
Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center - 80 - 5-3.
5-4. Wall mounted type ¢ Models: ASHG07KGTB, ASHG09KGTB, ASHG07KMCC, ASHG09KMCC, ASHG12KMCC, ASHG07KETA, ASHG09KETA, ASHG12KETA, ASHG07KETA-B, ASHG09KETA-B, and ASHG12KETA-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
Page 90
¢ Models: ASHG18KMTB, ASHG22KMTB, and ASHG24KMTB Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up...
Page 91
¢ Models: ASHG12KGTB, ASHG14KGTB, ASHG14KMTB, ASHG14KMCC, ASHG14KETA, and ASHG14KETA-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up...
5-5. Ceiling type ¢ Model: ABHG18KRTA Fan speed Operation mode Measuring conditions HIGH 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Side view 0.25...
Page 93
¢ Model: ABHG22KRTA Fan speed Operation mode Measuring conditions HIGH 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Side view 0.25 Vertical airflow direction louver: Up Horizontal airflow direction louver: Center...
5-6. Floor type ¢ Models: AGHG09KVCA, AGHG12KVCA, and AGHG14KVCA Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center UPPER LOWER Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
6. Fan performance 6-1. Mini duct type ¢ Model: ARXG07KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Quiet (SP mode 03) Hi (SP mode 03) Normal SP upper limit SP mode 00 upper limit SP mode 03 lower limit Hi (Normal SP) Hi (SP mode 00)
Page 96
Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 88 - 6-1. Mini duct type 6. Fan performance...
Page 97
¢ Model: ARXG09KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Hi (SP mode 03) Quiet (SP mode 03) SP mode 00 upper limit SP mode 03 lower limit Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) Airflow (m Available airflow rate range (High level)
Page 98
Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 90 - 6-1. Mini duct type 6. Fan performance...
Page 99
¢ Model: ARXG12KSLAP SP mode 03 upper limit Quiet (SP mode 03) Hi (SP mode 03) Quiet Normal SP (Normal SP) upper limit Quiet SP mode 03 (SP mode 00) lower limit SP mode 00 (Normal SP) upper limit Hi (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 03)
Page 100
Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 92 - 6-1. Mini duct type 6. Fan performance...
Page 102
Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 94 - 6-1. Mini duct type 6. Fan performance...
/h = 0.2778 l/s = 0.5886 CFM • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 7-1. Compact cassette type Airflow Model Operation mode Fan speed High Cooling AUXG07KVLA Quiet AUXG09KVLA High Heating Quiet High Cooling Quiet AUXG12KVLA High Heating...
7-2. Mini duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KSLAP High Heating Quiet High Cooling Quiet ARXG09KSLAP High Heating Quiet High Cooling Quiet ARXG12KSLAP High Heating Quiet High Cooling Quiet ARXG14KSLAP High Heating Quiet High Cooling Quiet ARXG18KSLAP High...
7-3. Slim duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KLLAP High Heating Quiet High Cooling Quiet ARXG09KLLAP High Heating Quiet High Cooling Quiet ARXG12KLLAP High Heating Quiet High Cooling Quiet ARXG14KLLAP High Heating Quiet High Cooling Quiet ARXG18KLLAP High...
7-4. Medium static pressure duct type Airflow Model Operation mode Fan speed High 1,100 Cooling Quiet ARXG22KMLB High 1,100 Heating Quiet - 114 - 7-4. Medium static pressure duct type 7. Airflow...
7-5. Wall mounted type Airflow Model Operation mode Fan speed High Cooling Quiet ASHG07KGTB High Heating Quiet High Cooling Quiet ASHG09KGTB High Heating Quiet High Cooling Quiet ASHG12KGTB High Heating Quiet High Cooling Quiet ASHG14KGTB High Heating Quiet High Cooling Quiet ASHG18KMTB High...
Page 124
Airflow Model Operation mode Fan speed High 1,170 Cooling Quiet ASHG24KMTB High 1,170 Heating Quiet High Cooling Quiet ASHG07KMCC High Heating Quiet High Cooling Quiet ASHG09KMCC High Heating Quiet High Cooling Quiet ASHG12KMCC High Heating Quiet High Cooling Quiet ASHG14KMCC High Heating Quiet...
Page 125
Airflow Model Operation mode Fan speed High Cooling ASHG09KETA Quiet ASHG09KETA-B High Heating Quiet High Cooling ASHG12KETA Quiet High ASHG12KETA-B Heating Quiet High Cooling ASHG14KETA Quiet ASHG14KETA-B High Heating Quiet - 117 - 7-5. Wall mounted type 7. Airflow...
7-6. Ceiling type Airflow Model Operation mode Fan speed High Cooling Quiet ABHG18KRTA High Heating Quiet High Cooling Quiet ABHG22KRTA High Heating Quiet - 118 - 7-6. Ceiling type 7. Airflow...
7-7. Floor type Airflow Model Operation mode Fan speed High Cooling Quiet AGHG09KVCA High Heating Quiet High Cooling Quiet AGHG12KVCA High Heating Quiet High Cooling Quiet AGHG14KVCA High Heating Quiet - 119 - 7-7. Floor type 7. Airflow...
8-8. Sound level check point ¢ Compact cassette type Microphone 1.5 m Microphone - 139 - 8-8. Sound level check point 8. Noise level curve...
Page 148
¢ Mini duct type, Slim duct type, and Medium static pressure duct type Product Measuring duct Measuring duct (Set the static pressure as rating in this area.) Microphone Microphone Front view Side view ¢ Wall mounted type Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above.
10. Safety devices Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse AUXG07KVLA AUXG09KVLA Activate: 100 ±15 °C Fan motor stop AUXG12KVLA Compact cassette Reset: 95 ±10 °C AUXG14KVLA AUXG18KVLA Fan motor restart...
Page 152
Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse AGHG09KVCA Activate: 150 ±15 °C Fan motor stop AGHG12KVCA Floor 250V, 5.0 A 110 °C Off ― Reset: 120 ±15 °C AGHG14KVCA Fan motor restart *: Printed Circuit Board - 144 - 10.
11. External input and output 11-1. Compact cassette type, Mini duct type, Slim duct type, and Medium static pressure duct type Exterior of the indoor unit PCB and the component location differ by the type of the indoor unit as follows.
Page 154
¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. •...
Page 155
¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input External output Mode Function setting Terminal CN47 60—00...
Page 156
¢ Details of function Control input function • When function setting is "Operation/Stop" mode 1 Function setting External input Input signal Command Off → On Operation 46—00 Terminal On → Off Stop Input Operation Indoor unit Stop Remote controller NOTES: •...
Page 157
• When function setting is "Operation/Stop" mode 2 Function setting External input Input signal Command Off → On Operation 46—03 Terminal On → Off Stop (R.C. disabled) Input Operation Indoor unit Stop (R.C. disabled) Remote controller NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
Page 158
Indoor unit fan operation status Function setting External output Output signal Command Low → High Fan run 60—10 CN47 High → Low Fan stop Output signal Condition The indoor unit fan is operating. Low → High The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation.
11-2. Wall mounted type (KGTB, KMTB, KETA, and KETA-B) External input and output PCB SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 To CN6 on Indoor unit PCB Input External input External output Connector Input select signal Operation/Stop CN313/ Edge/Pulse Dry contact/...
Page 160
¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
Page 161
¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. External input and output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
Page 162
¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
Page 163
Input signal type External input and output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and out- put PCB. The width of pulse must be longer than 200 msec.
Page 164
¢ Details of function Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Operation External input and 46-00...
Page 165
• When function setting is "Forced stop" mode – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Forced stop External input and 46-02 60-00 / 1 CN313 output PCB...
Page 166
• When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Operation External input and 46-03 60-00 / 1 CN313 Stop (R.C.
Page 167
• Forced thermostat off function Rotary SW on Function External input and External input Input signal Command setting / output PCB Thermostat 60-00 / 2 Off → On External input and output 60-09 / B CN313 Normal On → Off 60-10 / C operation Input...
Page 168
Control output function • Operation/Stop status Rotary SW on Function Output External input and External output Command setting / signal output PCB Off → On Operation External input and output 60-00 / 1 CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
11-3. Wall mounted type (KMCC) With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details. CNB02 —...
Page 170
• Circuit diagram example • Contact capacity: DC 24 V or more, 10 Indoor unit mA or more. Communication kit Connected unit control PCB • *: Make the distance from the PCB to Example: Switch Connector the connected unit within 10 m. •...
Page 171
• Optional part Part name Model name Exterior External input wire External connect kit UTY-XWZXZ5 Communication kit UTY-TWBXF2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5). - 163 - 11-3.
Page 172
¢ External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device. Operation status output Air conditioner operation status signal can be output. •...
Page 173
Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
Page 175
External input and output PCB The indoor unit Operation/Stop can be set by using the input terminal on the PCB. Input select Use either one of these types of terminals according to the application. (Both types of terminals cannot be used simultaneously.) •...
Page 176
¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
Page 177
¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
Page 178
Input signal type • Indoor unit Input signal type is only "Edge". Edge • External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
Page 179
¢ Details of function Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Pulse" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Input 1 Pulse Operation External input and...
Page 180
• When function setting is "Forced stop" mode – In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Forced stop Input of indoor unit Terminal On →...
Page 181
• When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Input of indoor unit Terminal Stop (R.C.
Page 182
Forced thermostat off function Function Rotary SW of External External input Input signal Command setting / input and output PCB 60-00 / 2 Off → On Thermostat off 60-09 / B External input and output Input 1 60-10 / C Normal On →...
Page 183
Error status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Error 60-09 / B Output of indoor unit CN47 High → Low Normal Off → On Error 60-00 / 2 Output 1 On →...
Page 184
External heater output Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Heater on 60-11 / D Output of indoor unit CN47 High → Low Heater off 60-00 / 2 Off →...
11-5. Floor type Indoor unit PCB CN 23 CN 21 CN 15 CN 14 P 190 External input External output Connector Input signal Operation/Stop CN14 Forced stop — Edge Forced thermostat off CN15 Operation status Indoor unit Error status CN20/CN21/ —...
Page 186
¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m . •...
Page 187
¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input Function Mode Indoor unit setting CN14 CN15...
Page 188
¢ Details of function Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 On → Off Stop 46-00 Input of indoor unit...
Page 189
• When function setting is "Operation/Stop"mode 2 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 Stop (R.C. On → Off disabled) 46-03 Input of indoor unit Off → On Operation 60-00 CN15...
Page 190
Control output function • Operation/Stop status Output Mode Function setting External output Command signal Low → High Operation 60-00 CN15 High → Low Stop Output of indoor unit Off → On Operation 60-00 CN20 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
Page 191
• Indoor unit fan operation status Output Mode Function setting External output Command signal Low → High Fan run 60-10 CN15 High → Low Fan stop Output of indoor unit Off → On Fan run 60-00 CN22 On → Off Fan stop Output signal Condition...
Page 192
• Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 184 - 11-5.
Page 193
• Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
12. Group connection NOTE: Group control cannot be used together with Wireless LAN adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
Page 195
2. Set the R.C. address. (Function setting) • Addresses will be automatically set when initially starting up this unit. In such a case, do not change the remote controller address for the indoor unit, and keep it at the initial setting of “00”.
13. Remote controller 13-1. Wireless remote controller (AR-REW4E, AR-REM4E, and AR-REB1E) ¢ Overview • AR-REW4E Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button...
Page 197
To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current oper- ation. • AR-REM4E Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button...
Page 198
• AR-REB1E Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button CLOCK ADJUST button TIMER CANCEL button NOTE: Functions may differ by type of the indoor unit.
Page 199
¢ Specifications Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries) Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
13-6. Wired remote controller (UTY-RNNGM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
Page 210
¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
Page 211
¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Front view Side view Size (H × W × D) 120 × 120 × 18 Weight Cable length (accessory) Power Wiring specifications Cable size Wire type Remarks Remote controller cable...
Page 212
When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
13-7. Wired remote controller (UTY-RLRG: Optional part) ¢ Overview a LED lamp (Operation indicator) Lights while the indoor unit is operating. Blinks when an error occurred. b FAN button Each time the button is pressed, fan speed switches as follows: Auto High Quiet...
Page 214
¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
Page 215
¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Hole: 9 × 4.5 Hole: 12.5 × 4.5 Hole: 6 × 4.5 Front view Side view Rear view Size (H × W × D) 120 ×...
13-8. Wired remote controller (UTY-RVNGM: Optional part) ¢ Overview a Display panel (with backlight) b Screen switch button (Left) c Menu button d Cancel button e Cursor button f Screen switch button (Right) g Power indicator h On/off button i Enter button - 208 - 13-8.
Page 217
¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
Page 218
¢ Specifications Unit: mm 21.3 Front view Side view Size (H × W × D) 120 × 120 × 21.3 Weight Wiring specifications Cable size Wire type Remarks Remote controller cable Polar 3 core Use sheathed PVC cable. 0.33 mm - 210 - 13-8.
Page 219
¢ Installation (Remote control main unit) Installation space: Unit : mm or more or more or more 220 or more* NOTE: Secure enough space where a flat-blade screwdriver to remove the case can be inserted. Installation procedures: 1. Process the remote controller cable. Unit : mm 1.
Page 220
3. Attach the remote controller. • When attaching to switch box: a. Seal the wiring hole of the remote controller cable. b. Put a remote controller cable through the hole of the rear case. c. Fix the rear case by securing it with attached screws (2 places). •...
Page 221
4. Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2 N•m 1. 12V (Red) 2. Signal (White) 3.
Page 222
5. Attach the front case. • Insert after adjusting upper part of front case. • When insert the front case, do not pinch the cable. Front case Click! Good Prohibited Prohibited Prohibited CAUTION Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off. ¢...
Page 223
When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
13-9. Wired remote controller (UTY-RNRGZ*: Optional part) ¢ Overview a Remote temperature sensor (inside) b On/off button Operable only while displaying the “Monitor mode” screen. c LED lamp (operation indicator) d Touch panel display e Set temperature Operating temperature can be set. f Remote controller group name g Mode Operation mode can be set.
Page 225
¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
Page 226
¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. [Unit : mm] 20.4 Model name UTY-RNRGZ* Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) 120 × 120 × 20.4 Weight Input voltage DC 12...
13-10. Simple remote controller (UTY-RSNGM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
Page 228
¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
Page 229
¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm hole x 2 hole x 2 Front View Side View Rear View Size (H × W × D) 120 × 75 × 14 Weight Cable length (accessory) Power ...
Page 230
When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
13-11. Simple remote controller (UTY-RSRG and UTY-RHRG: Optional parts) ¢ Overview a LED lamp Lights during operation. b Louver button Adjusts the airflow direction. c START/STOP button Starts and stops operation. d FAN control button Switches the fan speed as follows: Auto High Quiet...
Page 232
¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
Page 233
¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm 30.0 30.0 Hole: 9 × 4.5 23.0 Hole: 6 × 4.5 Hole: 12.5 × 4.5 Front View Side View Rear View Size (H × W × D) 120 ×...
14. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 14-1. Compact cassette, Mini duct, Slim duct types indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings.
Page 235
¢ DIP switch setting • SW100: Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. The slide switches are normally set to make the unit number 00. Remote Switch number controller...
14-2. Indoor unit (setting by wireless remote controller) CAUTION This setting changes the function settings used to control the indoor unit according to the installa- tion conditions. Incorrect settings can cause a product malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
Page 237
¢ AR-REM4E (for Wall mounted type KGTB), AR-REW4E (for Wall mounted type KETA), AR-REW2E (for Wall mounted type KMTB), and AR-REM7E (for Floor type) Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller.
Page 238
To enter the function setting mode, while holding down the POWERFUL and TEMP. button, press the RESET button. POWERFUL TEMP. ( RESET Function setting mode display - 230 - 14-2. Indoor unit (setting by wireless remote controller) 14. Function settings...
Page 239
Select the function number by pressing the or the buttons. Each time the 10 °C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the POWERFUL button. (To return to the function number selection, press the POWERFUL button again.) Select the function number by pressing the or the...
Page 240
Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 2 short beeps NOTE: Press button within 30 seconds after pressing MODE button.
Page 241
Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
Page 242
Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the TEMP.
Page 243
¢ AR-REB1E (for Wall mounted type KMCC) Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details. 10°C HEAT button POWERFUL button Changes the displayed digits.
Page 244
Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the POWERFUL button. (To return to the function number selection, press the POWERFUL button again.) Select the function number by pressing the or the...
Page 245
Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 2 short beeps NOTE: Press button within 30 seconds after pressing MODE button.
Page 246
Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
Page 247
Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
Page 248
¢ UTY-LNTG (for Compact cassette type) or AR-REJ1E (included in UTY-LBTGM for Duct type) Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details.
Page 249
Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the ECONOMY button. (To return to the function number selection, press the ECONOMY button again.) Select the function number by pressing the or the...
Page 250
Press the button once to transmit the function setting information. 1 short beep will be emit- ted from the indoor unit or the IR receiver when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 1 short beep NOTE: Press button within 30 seconds after pressing MODE button.
Page 251
Setting up each indoor unit Repeat step from 1. to 8. to set up each indoor unit. If the custom code is other than " ", steps from 1. to 2. and 8. need to be performed. Resetting the power after setting up all indoor units Important: •...
Page 252
Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
14-3. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
Page 254
¢ UTY-RNNGM Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
Page 255
Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
Page 256
¢ UTY-RLRG Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Page 257
Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button. Function number Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button. Setting number Example: Function number 30 Setting number 01 Error Good...
Page 258
¢ UTY-RVNGM Function setting procedure Connect the power supply of the outdoor unit. Switch to the function setting mode. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor”...
Page 259
Select the [Function No.] with pressing the [Cursor button (Left/Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)]. Function setting Mo 10:00AM R.C. Function Setting address Cancel: Version Error history Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button (Up/Down)].
Page 260
When [Cancel button] is pressed twice while “Function setting” screen is displayed, it switches to the “Submenu” screen. Function setting Mo 10:00AM R.C. Function Setting Submenu Mo 10:00AM address Date and time Screen Cancel: Filter sign Version Error history R.C. sensor control Room temp.
Page 261
¢ UTY-RNRGZ* Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Page 262
“Function No.” screen is displayed. Set the “Function No.” with Function No. Cancel When the “OK” is touched, the display returns to the “Function Setting” screen. Touch the “Function No.” on the “Function Setting” screen. Function Setting Address [002–01] Function No. [30] Setting No.
Page 263
Touch the “Yes” of the verification screen. Function Setting Function setting will be performed. OK? In case of “ERROR” In case of “OK” Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Function No. [30] Setting No. [01] Setting No.
14-4. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
Page 265
¢ UTY-RSNGM Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
Page 266
Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
Page 267
Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
Page 268
¢ UTY-RSRG/UTY-RHRG Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
Page 269
Select the item number to be set with the SET TEMP. or SET TEMP. button, and press button to switch to the setting screen. Select the “13” in Menu 2-F1 settings. Then, press the button. Select the 2-wire remote controller address with the SET TEMP. or SET TEMP.
Page 270
Setting results are displayed after data transmission. Press the button to return to the 2-wire remote controller address selection screen of step 9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item se- lection screen.
14-5. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Medium Wall mounted Function...
Page 272
1) Remote controller address setting (for Wall-mounted type only) NOTES: • Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. • This setting is configurable only by wireless remote controller, but not configurable by Polar 3- wired remote controller.
Page 273
3) Ceiling height (for Compact cassette type and Ceiling type only) Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 3. "Dimensions"...
Page 274
6) Static pressure (for Mini duct type and Slim duct type) Select the appropriate static pressure according to the installation conditions. For mini duct type: Function number Setting value Setting description Factory setting 0 Pa 10 Pa 20 Pa 30 Pa 40 Pa 50 Pa Standard...
Page 275
8) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
Page 276
9) Room temperature control for wired remote controller sensor (for other than Floor type) Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Page 277
12) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 13) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 278
16) Switching functions for external output terminal (For other than KM and KE models in Wall-mounted type) Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦...
14-6. Wired remote controller (UTY-RNNGM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
Page 280
SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
14-7. Wired remote controller (UTY-RVNGM) Memory backup setting DIP switch 1 Dual remote controller setting ¢ Switch location ¢ DIP switch setting SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
14-8. Wired remote controller (UTY-RLRG) DIP switch Memory backup setting ¢ Switch location Front case (back side) Set the DIP switch to ON ¢ Dip switch setting SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
14-10. Simple remote controller (UTY-RSNGM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
15-2. Mini duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, and ARXG14KSLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose Operating manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation...
Page 286
¢ Model: ARXG18KSLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose Operating manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation Cable tie (medium) (small) Insulation...
15-3. Slim duct type ¢ Models: ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP, and ARXG18KLLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (Large) Installation manual Cable tie (Small) Installation template Drain hose Washer Hose band Coupler heat insulation Drain hose insulation B (Large) Coupler heat insulation...
15-6. Ceiling type ¢ Models: ABHG18KRTA and ABHG22KRTA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Insulation Operating manual Drain hose (CD-ROM) Installation manual Hose band Template Cable tie (large) M10 nut A Cable tie (small) (with flange) M10 nut B Remote controller cable (with spring lock...
17. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
Page 302
Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 30 °C RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
Page 303
Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 30 °C Figure 17-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
Page 304
- 296 - 17-2. Points to remember when installing 17. Indoor unit installation precautions...
1. Specifications Type Inverter heat pump Model name AOHG30KBTA4 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ASHG07KMCC ×4 Rated Btu/h 27,300 Cooling 2.4—10.1 Min.—Max. Btu/h 8,200—34,500 Capacity Rated Btu/h 32,800 Heating 3.0—11.2 Min.—Max.
Page 307
Specifications for ErP Lot10 Model name AOHG30KBTA4 Cooling Energy efficiency class Heating (Average) Cooling 8.0 (35 °C) Pdesign Heating (Average) 6.5 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 1,978 Cooling Sound power level HIGH dB (A) Heating...
2. Dimensions 2-1. Model: AOHG30KBTA4 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 300 - 2-1. Model: AOHG30KBTA4 2. Dimensions...
3. Installation space 3-1. Model: AOHG30KBTA4 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 310
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Page 311
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity table 6-1. Combinations ¢ Model: AOHG30KBTA4 Cooling Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max.
Page 315
Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.33 1.33 2.67 2.67 8.00 10.1...
Page 316
Heating Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class —...
Page 317
Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class 1.37 2.35 2.35 3.53 9.60...
6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOHG30KBTA4 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOHG30KBTA4 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96...
Page 337
NOTES: • TC: Total Capacity (kW), IP: Input Power (kW) • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit) •...
7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOHG30KBTA4 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
11. Electrical characteristics Model name AOHG30KBTA4 Voltage 230 ~ Power supply Frequency 18.5 Maximum operating current * Starting current Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
12. Safety devices Model Type of Protection form protection AOHG30KBTA4 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10 °C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10 °C Reset Fan motor restart...
13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
Page 360
¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
Page 361
¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
Page 364
¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
Page 365
After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
Page 366
[How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
Page 367
c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
Page 368
¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
Page 371
¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
Page 372
Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant piping. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
Page 374
7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
16. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 16-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
1. Specifications Type Inverter heat pump Model name AOHG36KBTA5 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ASHG07KMCC ×5 Rated Btu/h 32,400 Cooling 3.0—11.0 Min.—Max. Btu/h 10,200—37,500 Capacity 10.6 Rated Btu/h 36,200 Heating 3.5—12.0...
Page 379
Specifications for ErP Lot10 Model name AOHG36KBTA5 Cooling Energy efficiency class Heating (Average) Cooling 9.5 (35 °C) Pdesign Heating (Average) 7.0 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 2,130 Cooling Sound power level HIGH dB (A) Heating...
2. Dimensions 2-1. Model: AOHG36KBTA5 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 372 - 2-1. Model: AOHG36KBTA5 2. Dimensions...
3. Installation space 3-1. Model: AOHG36KBTA5 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 382
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Page 383
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity table 6-1. Combinations ¢ Model: AOHG36KBTA5 Cooling Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max.
Page 387
Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — 1.90 1.90 1.90 3.80 —...
Page 388
Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.33 1.33 1.71 1.71 3.42 9.50...
Page 389
Heating Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — —...
Page 390
Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — 1.55 1.55 2.64 4.86 —...
Page 391
Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class 1.50 1.95 1.95 2.60 2.60 10.60...
6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOHG36KBTA5 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOHG36KBTA5 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88...
7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOHG36KBTA5 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
11. Electrical characteristics Model name AOHG36KBTA5 Voltage 230 ~ Power supply Frequency 20.0 Maximum operating current * Starting current 11.1 Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
12. Safety devices Model Type of Protection form protection AOHG36KBTA5 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10 °C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10 °C Reset Fan motor restart...
13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
Page 434
¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
Page 435
¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
Page 438
¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
Page 439
After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
Page 440
[How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
Page 441
c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
Page 442
¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
Page 445
¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
Page 446
Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant piping. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
Page 448
7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
15. Accessories 15-1. Model: AOHG36KBTA5 Part name Exterior Q’ty Part name Exterior Q’ty Adapter K: mm (in) Installation manual 12.70 (1/2) to 9.52 (3/8) Adapter H: mm (in) Drain pipe 9.52 (3/8) to 12.70 (1/2) Cable tie (small) - 441 - 15-1.
16. Optional parts Exterior Part name Model name Summary Set temperatures on timers to best meet individuals’ needs. Includes a large backlit LCD and 4-way navigation pad. Remote controller cable: 0.33 mm² (22AWG) NOTES: • The remote controller cable supplied with this controller is for indoor use.
17. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
Need help?
Do you have a question about the AUXG07KVLA and is the answer not in the manual?
Questions and answers