7) Chassis Final Connections
With the chassis in place, you are now ready to begin chassis
connections:
A. Move the thermostat switches to "OFF" and "AUTO." This
will keep the ther mo stat from cy cling the chassis until fi nal
connections are com plete.
B. Connect the ductwork onto the 10" collar. Plas tic wireties (fi eld
sup plied) are suggested to se cure the ductwork in place. Use
2 wire ties, one for each inner and outer fl ex duct sleeve.
D. For 208 Volt pow er only: you must move the trans form er wire
as shown in Fig ure 8, Page 9.
E. Review the Fi nal Installation Check list on Page 12 before
re plac ing the pow er quick dis con nect, reconnecting power
to the chassis, plug ging in the re mote ther mo stat har ness, or
op er at ing the chassis.
Electrical shock and moving parts hazard can cause injury
or death. If you have not done so, pull out the disconnect
head found on the front of chas sis before continuing instal-
lation! Disconnect external power at the breaker.

8) Final Installation Checklist

Correct line voltage?
Chassis deck level?
Plenum divider baffl e installed?
Wall plenum caulked? Level? Flashing?
HACR type breaker/fuse?
Single circuit only?
Ductwork connected?
Chassis weather seal in place?
Wall thermostat wired correctly?
Chassis inserted into plenum?
12
920-159-02
RT4 Digital Thermostat
III. Chassis Operation
9) Remote Thermostat Control
The chassis requires a simple single stage heat-cool wall thermostat.
Each chassis comes with a terminal strip located in the electrical
control box. All internal chassis wiring (low & high voltage) is factory
ready for 230 Volt operation. For 208 Volt operation a single wire
MUST BE CHANGED ON THE TRANS FORM ER. Refer to Figure
8 on page 9.
10) Low Ambient Protection
Each chassis is equipped with Low Ambient Protection in the form of
a suction line thermostat. This thermostat will prevent compressor
operation at low suction line temperatures. Each chassis is also
equipped with a factory in stalled bellows that will drain water from
the base pan to prevent the fan slinger from freezing during winter
weather.
11) Heating Defrost
All Heat Pumps have a passive heating defrost system. Defrost
occurs as needed and automatically switches to electric heat during
defrost. When the outdoor ambient temperature drops below a 45°F
factory setting, the chassis au to mat i cal ly switch es to electric heat.
As outdoor ambient temperatures rise above 45°F, the chassis
returns to the heat pump mode. The changeover temperature is user
adjustable from approximately 32°F - 55°F. The defrost thermostat
may also be used to lock out the compressor in an emergency
heat situation.
(Heat Pump Models Only)