Safety Test - With Gas Ball Valve Closed - Riello RS 25/M BLU Installation, Use And Maintenance Instructions

Forced draught gas burners, progressive two-stage or modulating operation
Table of Contents

Advertisement

Available languages

Available languages

SAFETY COMPONENT
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic cam) (if present)
Oil valve (solenoid)(if present)
Oil regulator (if present)
Oil pipes/ couplings (metallic) (if present)
Flexible hoses (if present)
Fan impeller
(A)
LIFE CYCLE
10 years or 250.000 operation cycles
10 years or 250.000 operation cycles
10 years or 250.000 operation cycles
10 years or 250.000 operation cycles
15 years
10 years or 250.000 operation cycles
10 years or 250.000 operation cycles
10 years or 250.000 operation cycles
10 years
5 years or 30.000 pressurised cycles
10 years or 500.000 start-ups
17
SAFETY TEST - WITH GAS BALL VALVE
CLOSED
It is fundamental to ensure the correct execution
of the electrical connections between the gas so-
lenoid valves and the burner to perform safely
the commissioning.
For this purpose, after checking that the connec-
tions have been carried out in accordance with
the burner's electrical diagrams, an ignition cycle
with closed gas ball valve -dry test- must be per-
formed.
1 The manual ball gas valve must be closed
2 The electrical contacts of the burner limit
switch need to be closed
3 Ensures closed the contact of the low gas
pressure switch
4 Make a trial for burner ignition.
The start-up cycle must be as follows:
– Starting the fan for pre-ventilation
– Performing the gas valve seal control, if pro-
vided
– Completion of pre-ventilation
– Arrival of the ignition point
– Power supply of the ignition transformer
– Electrical Supply of solenoid gas valves
Since the manual gas ball valve is closed, the
burner will not light up and its control box will go
to a safety lockout condition.
The actual electrical supply of the solenoid gas
valves can be verified by inserting a tester.
Some valves are equipped with light signals (or
close/open position indicator) that turn on at the
same time as their power supply.
IF THE ELECTRICAL SUPPLY OF
THE GAS VALVES OCCURS AT
UNEXPECTED TIMES, DO NOT
OPEN
MANUAL
WARNING
VALVE, SWITCH OFF POWER
LINE; CHECK THE WIRES; COR-
RECT THE ERRORS AND REPEAT
THE COMPLETE TEST.
SAFTEY COMPONENTS
The safety components must be replaced at the
end of their life cycle indicated in table (A).
The specified life cycles do not refer to the war-
ranty terms indicated in the delivery or payment
conditions.
GAS
BALL