Diagnostics and troubleshooting
11.4 Status messages according to NE 107
F017
Adjustment span too
small
F025
Error in the linearization
table
F036
No operable software
F040
Error in the electronics
F080
General software error
F105
Determine measured
value
F260
Error in the calibration
F261
Error in the transmitter
settings
F265
Measurement function
disturbed
Function check
C700
Simulation active
36
Code
Text message
Adjustment not within
specification
Index markers are not
continuously rising, for
example illogical value
pairs
Checksum error if soft-
ware update failed or
aborted
Limit value exceeded in
signal processing
Hardware error
General software error
The transmitter is still
in the start phase, the
measured value could
not yet be determined
Checksum error in the
calibration values
Error in the EEPROM
Error during setup
Auto false each suppres-
sion faulty
Error when carrying out
a reset
Program sequence of
the measuring function
disturbed
Code
Text message
A simulation is active
Cause
Rectification
Change adjustment
according to the limit
values (difference be-
tween min. and max.
≥ 10 mm)
Check linearisation ta-
ble
Delete table/Create new
Repeat software update
Send transmitter for re-
pair
Restart transmitter
Send transmitter for re-
pair
Restart transmitter
Wait for the end of the
switch-on phase
Duration up to 3 min-
utes depending on the
measurement environ-
ment and parameter
settings
Send transmitter for re-
pair
Repeat setup
Carry out a reset
Device restarts automat-
ically
Cause
Rectification
Finish simulation
Wait for the automatic
end after 60 mins.
DevSpec
State in CMD 48
Byte 5, Bit 1 of
Byte 0 ... 5
Byte 5, Bit 2 of
Byte 0 ... 5
Byte 5, Bit 3 of
Byte 0 ... 5
Byte 5, Byte 5, Bit 4 of
Byte 0 ... 5
Byte 5, Byte 5, Bit 5 of
Byte 0 ... 5
Byte 5, Byte 5, Bit 6 of
Byte 0 ... 5
Byte 4, Bit 0 of
Byte 0 ... 5
Byte 4, Bit 1 of
Byte 0 ... 5
Byte 4, Bit 3 of
Byte 0 ... 5
DevSpec
State in CMD 48
"Simulation Active" in
"Standardized Status 0"