Status messages
The status messages are divided into the following categories:
and explained by pictographs:
1
2
3
4
Figure 11.1
Failure: Due to a malfunction in the transmitter, a fault message is output.
This status message is always active. It cannot be deactivated by the user.
Function check: The transmitter is being worked on, the measured value is tem-
porarily invalid (for example during simulation).
This status message is inactive by default.
Out of specification: The measured value is unreliable because an transmitter speci-
fication was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance: Due to external influences, the transmitter function is limited. The
measurement is affected, but the measured value is still valid. Plan in maintenance
for the transmitter because a failure is expected in the near future (e.g. due to
buildup).
This status message is inactive by default.
Failure
F013
no measured value
available
SITRANS LR110
Operating Instructions, 01/2020, A5E49829006
Failure
Function check
Out of specification
Maintenance requirement
Failure - red
Out of specification - yellow
Function check - orange
Maintenance - blue
Pictographs of the status messages
Code
Text message
No measured value in
the switch-on phase or
during operation
11.4 Status messages according to NE 107
Cause
Rectification
Check or correct instal-
lation and/or parameter
settings
Clean the antenna sys-
tem
Diagnostics and troubleshooting
DevSpec
State in CMD 48
Byte 5, Bit 0 of
Byte 0 ... 5
35