Advertisement

5 Installation Procedure
Wire Gauges, Tightening Torques, and Crimp Terminals
Wire Gauges and Tightening Torques
Wire gauge and torque specifications are listed in
Tightening
Terminal
Screw
Torque
signal
Size
N m (in lb)
V1, V2,
0.22 to 0.25
M2
AC, FE
(1.95 to 2.21)
Crimp Terminals
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent to crimp the
terminals with the specifications listed in
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
6 mm
d2
d1
L
Terminal Functions
Terminal
V1
Analog voltage output 1
V2
Analog voltage output 2
AC
Common
FE
Ground
<1> Set the functions and output levels for terminals V1 and V2 using drive parameters. See the drive Quick Start
Guide or Technical Manual for directions on setting parameters.
20
Table 2 Wire Gauges and Tightening Torques
Bare Cable
Applicable
Gauges mm
Stranded wire:
0.25 to 1.0
(24 to 17 AWG)
Solid wire:
0.25 to 1.5
(24 to 16 AWG)
Table 3 Crimp Terminal Sizes
Phoenix Contact
2
Wire Gauge mm
0.25 (24 AWG)
0.34 (22 AWG)
0.5 (20 AWG)
Table 4 Option Terminal Functions
Function
Signal Level
-10 to 10 V
YASKAWA ELECTRIC TOBP C730600 40B 1000-Series Option AO-A3 Installation Manual
Table
2.
Recomm.
Applicable
2
2
Gauge mm
Gauges mm
0.75
(18 AWG)
(24 to 20 AWG)
Table 3
to ensure proper connections.
Model
mm (in)
AI 0.25 - 6YE
10.5 (13/32)
AI 0.34 - 6TQ
10.5 (13/32)
AI 0.5 - 6WH
14 (9/16)
• Analog voltage output for an external monitoring
device
<1>
Output resolution 11-bit plus sign (1/2048)
• Max. load current 3 mA
0 V
Common for analog voltage output
Used for grounding shielded lines
Crimp Terminals
Recomm.
2
Gauge mm
0.25 to 0.5
0.5
(20 AWG)
L
d1
mm (in)
0.8 (1/32)
0.8 (1/32)
1.1 (3/64)
Description
Wire
Type
2
Shielded
twisted
pair, etc.
d2
mm (in)
2 (5/64)
2 (5/64)
2.5 (3/32)

Advertisement