DSE Model 5310 Automatic Mains Failure & Instrumentation System Operators Manual
7 INSTALLATION INSTRUCTIONS
The model DSE 5310 Module has been designed for front panel mounting. Fixing is by 4 clips for easy assembly.
7.1 PANEL CUT-OUT
160.00mm
(6.3")
Maximum panel thickness – 8mm (0.3")
In conditions of excessive vibration the module should be mounted on suitable anti-vibration mountings.
7.2 COOLING
The module has been designed to operate over a wide temperature range -30 to +70º C . Allowances should be
made for the temperature rise within the control panel enclosure. Care should be taken NOT to mount possible
heat sources near the module unless adequate ventilation is provided. The relative humidity inside the control
panel enclosure should not exceed 95% .
7.3 UNIT DIMENSIONS
220.00mm
(8.7")
FIG 3
Panel cutout 220mm x 160mm ( 8.7" x 6.3")
FIG 4
Part No. 057-013 5310 OPERATING MANUAL ISSUE 7.1 18/06/2007 ADM
35