5.5.3 Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP
switches of a new product are set to 'off', except for DS-2).
DS-1 Panel option
off
DS-2 Panel option
DS-3 Ch. voltage
off
DS-4 Ch. voltage
off
DS-5 Frequency
off
DS-6 Search mode
off
DS-7 AC-in Limit
off
DS-8 Store setting
→ ←
Example 1: (factory setting)
1
No panel or remote
switch connected
2
No panel or remote
switch connected
3, 4
GEL 14.4 V
5
Frequency: 50Hz
6
Search mode off
7
AC-in Limit 12 Amp
8 Store setting: off→ on→ off
Store the settings (DS3-DS7) by changing switch ds-8 from off to on, and then back to off.
The LED's 'charger' and 'alarm' will flash to indicate acceptance of the settings.

6. MAINTENANCE

The Compact does not require specific maintenance. It will suffice to check all connections
once a year. Avoid moisture and oil/soot/vapours, and keep the device clean.
22
DS-1
off
on
DS-2
on
DS-3
off
DS-4
on
DS-5
off
DS-6
off
DS-7
on
DS-8
→ ←
Example 2
1
No panel or remote
switch connected
2
No panel or remote
switch connected
3,4
AGM 14,7V
5
Frequency: 50Hz
6
Search mode off
7
AC-in Limit
8 Store setting: off→ on→ off
DS-1
DS-2
off
DS-3
DS-4
DS-5
DS-6
DS-7
off
DS-8
→ ←
Example 3
1
Panel or remote
switch connected
2
Panel or remote
switch connected
3, 4
Tubular plate 15V
5
Frequency: 60Hz
6
Search mode on
7
AC-in Limit
4 Amp
8 Store setting: off→ on→ off
on
on
on
on
on
12 Amp