3-1. SPECIFICATIONS
MUY-GE15NA-1 MUY-GE18NA-1
Model name
Capacity
Rated (Minimum~Maximum)
Power consumption
Rated
(Minimum~Maximum)
EER
[SEER] 3
1
Power supply
Max. fuse size (time delay)
Min. circuit ampacity
Fan Motor (ECM)
Compressor
Refrigerant control
Sound level 1
Defrost method
Dimensions
Weight
External finish
Remote controller
Control voltage (by built-in transformer)
Refrigerant piping
Refrigerant pipe size
(Min. wall thickness)
Connection method
Between the indoor & out-
door units
Refrigerant charge (R410A)
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2:
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB
Due to continuing improvement, above specification may be subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
Cooling 1
Btu/h
Cooling 1
W
Cooling
V , phase , Hz
A
A
F.L.A
Model
R.L.A
L.R.A
Fl.Oz.
Refrigeration oil
(Type)
Cooling
dB(A)
W
in.
D
in.
H
in.
Ib.
VDC
Liquid
in.
Gas
in.
Indoor
Outdoor
Height difference
ft.
Piping length
ft.
M-Series - MSY/MUY-GE Wall-Mount Systems (July 2014)
MUY-GE15NA-1
14,000
( 3,100 ~ 18,200 )
1,080 (160~2,000)
13.0 [ 21.0 ]
208/230 , 1 , 60
15
12
0.50
SNB130FQBHT
6.8
8.5
15.2 (NEO22)
Linear expansion valve
49
Reverse Cycle
31-1/2
11-1/4
21-5/8
80
Munsell 3Y 7.8/1.1
Wireless type
12 - 24
Not supplied
1/4 (0.0315)
3/8 (0.0315)
Flared
Flared
40
65
2 lb. 9 oz.
Rated frequency
Rated frequency
Maximum frequency
MUY-GE18NA-1
17,200
( 3,700 ~ 18,700 )
1,640 (240~2,070)
10.5 [19.2]
14
0.93
10.0
12.5
54
33-1/16
13
33-7/16
119
50
100
3 lb. 7 oz.