3.2.7 Reading Adjust Menu

For
Temperature
Reading only,
not Process
Figure 3.6 Flow Chart for Reading Adjust Menu
ENTER READING ADJUST MENU:
Press a
Press d
Press a
READING ADJUST VALUE SUBMENU:
Press d
Press b & c 5) Press b and c buttons to enter a new Reading Adjust value
Press d
Reading Offset Adjust allows the user to fine tune a minor error of the
transducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ±R.ADJ).
Reading Adjust value is adjustable between -1999 to 9999.
3.2.8 Setpoint Deviation Menu / Field Calibration Menu
Figure 3.7 Flow Chart for Setpoint Deviation / Field Calibration
ENTER SETPOINT DEVIATION MENU:
Press a
Press d
Press a
1) Press a , if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a , if necessary, until Display advances to R.ADJ
Reading Adjust Menu.
4) Display flashes 1
(-1999 to 9999).
6) Display shows STRD stored message momentarily and then
advances to SP.DV Setpoint Deviation Menu.
1) Press a , if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a , if necessary, until Display advances to SP.DV
Setpoint Deviation Menu.