Lenovo RackSwitch G8332 Installation Manual page 45

Hide thumbs Also See for RackSwitch G8332:
Table of Contents

Advertisement

© Copyright 2015 Lenovo
Attention: The rack-mounting frame may not be able to support the weight of the
networking switch with only the front post mounting brackets (2-post application). If
the switch has an undesirable amount of sag, it is recommended to use a 4-post
mounting kit.
Attention: For earthquake stability, mount the switch in a 4-post rack.
Statement 26
CAUTION:
Do not place any object on top of rack-mounted devices.
To install the 1U air duct option in a 19" rack, complete the following steps.
1. Loosen and remove the mounting screws from both sides of the mounting rail
and set them aside to reuse for securing the foam carrier in the next step.
2. Place the half shears on the rear side of the foam carriers and use the M3.5
mounting rail screws to secure the foam carrier assemblies snugly against the
rear of the G8332 unit. Torque the screws to approximately 1.1 Nm ± 0.1 Nm
(10 inch-pounds).
Half shear
Mounting screws
Note: There are additional M3.5 screws in the air duct assembly kit.
Foam carrier snug against rear of unit
Chapter 3: Installing G8332 Hardware and Options
Reuse mounting screws
45