Mitsubishi Electric PUHZ-ZRP35VKA Service Manual page 23

Hide thumbs Also See for PUHZ-ZRP35VKA:
Table of Contents

Advertisement

9-3. INDOOR – OUTDOOR CONNECTING CABLE
The cable shall not be lighter than design 60245 IEC or 60227 IEC.
Outdoor power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
* The Max. cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
* The optional indoor power supply terminal kit is necessary
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
OCH527B
Max. 45m
Max. 50m
3
1.5 (polar)
3
2.5 (polar)
1
Min. 1.5
1
23
Wire No.
Size (mm²)
3
2.5 (polar) and S3 separated
Min. 2.5
Wire No.
Size (mm²)
Max. 120m
2
Min. 0.3
Max. 80m
1
Min. 2.5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents