Function Setting - Mitsubishi Electric PUHZ-ZRP35VKA Service Manual

Hide thumbs Also See for PUHZ-ZRP35VKA:
Table of Contents

Advertisement

12

FUNCTION SETTING

12-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set as necessary using the remote controller. The setting of function for each unit can only be done by
the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
Function
Power failure
OFF
automatic recovery
ON
Indoor temperature
Average data from each indoor unit
detecting *1
Data from the indoor unit with remote controller
Data from main remote controller
LOSSNAY
Not supported
connectivity
Supported (Indoor unit does not intake outdoor air through LOSSNAY)
Supported (Indoor unit intakes outdoor air through LOSSNAY)
Power supply
240V
voltage
220V, 230V
Frost prevention
2
(Normal)
temperature
3
Humidifier control
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Change of
Standard
defrosting control
For high humidity
Refrigerant leakage
70%(ZRP35,50)/ 80%(ZRP60-140)
setting (%)
50%(ZRP35,50)/ 60%(ZRP60-140)
*1 The functions above are available only when the wired remote controller is used. The functions are not available for floor
standing models.
Meaning of "Function setting"
mode02:indoor temperature detecting
No Indoor temperature(ta)=
No.1 Average data of the
sensor on all the
indoor units
No.2 The data of the sensor
on the indoor unit that
connected
with remote controller
No.3 The data of the sensor
on main remote
controller.
OCH527B
Settings
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
Initial
ta=(A+B)/2
setting
ta=A
ta=C
Mode No. Setting No.
01
02
03
04
15
16
17
21
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
(MAIN)
(SUB)
ta=(A+B)/2
ta=B
ta=C
95
: Initial setting
(when sent from the factory)
1
2
The setting is
1
applied to all
2
the units in the
3
same
1
refrigerant
2
system.
3
1
2
1
2
1
2
1
2
1
2
OUTDOOR
OUTDOOR
INDOOR
INDOOR
REMOTE
REMOTE
REMOTE
(MAIN)
(SUB)
(MAIN)
ta=A
ta=A
ta=A
ta=A
ta=C
ta=C
Remarks